54
4013
PID SLEEP DELAY
Time delay for the sleep function, see Figure 16. If the ACS 140 output
frequency is below a set level (parameter 4014
SLEEP
LEVEL
) longer than
PID
SLEEP
DELAY
, ACS 140 is stopped.
4014
PID SLEEP LEVEL
Level for activation of sleep function, see Figure 16. When the ACS 140 output
frequency falls below the sleep level, the sleep delay counter is started. When
the ACS 140 output frequency rises above the sleep level, the sleep delay
counter is reset.
Note! Sleep level comparison is also inverted when error value is inverted using
parameter 4005
ERROR
VALUE
INV
.
4015
WAKE-UP LEVEL
Level for deactivation of sleep function. This parameter sets a process actual
value limit for the sleep function (see Figure 16). When the actual value falls
below the limit, the sleep function is interrupted.
Figure 16
Sleep function operation.
Code Description
Frequency
SLEEP
LEVEL
Parameter 4014
Time
START
STOP
t<td
td
t
d =
SLEEP
DELAY
, Parameter 4013
WAKE
-
UP
LEVEL
Parameter 4015
Time
Actual Value