32
Group 11: Reference Select
Reference commands can be given from the control panel or from two
external locations. The selection between the two external locations is made
with parameter 1102
EXT
1/
EXT
2
SEL
. For more information on control
locations, refer to “APPENDIX”, starting page 57.
Code Description
1101
KEYPAD REF SEL
Selection of active control panel reference in local control mode.
1 =
REF
1 (Hz)
Control panel reference is given in Hz.
2 =
REF
2 (%)
Control panel reference is given as a percentage (%).
1102
EXT1/EXT2 SEL
Sets the input used for selecting the external control location, or fixes it to
EXT
1
or
EXT
2. The external control location of both Start/Stop/Direction commands
and reference is determined by this parameter.
1...5 = DI1...DI5
External control location 1 or 2 is selected according to the state of the selected
digital input (DI1 ... DI5), where deactivated =
EXT
1 and activated =
EXT
2.
6 =
EXT
1
External control location 1 (
EXT
1) is selected. The control signal sources for
EXT
1 are defined with parameter 1001 (Start/Stop/Direction commands) and
parameter 1103 (reference).
7 =
EXT
2
External control location 2 (
EXT
2) is selected. The control signal sources for
EXT
2 are defined with parameter 1002 (Start/Stop/Direction commands) and
parameter 1106 (reference).
8 = C
OMM
External control location 1 or 2 is chosen through serial communication.