Group 25: Critical Freq
In some mechanical systems, certain speed ranges can cause resonance
problems. With this parameter group, it is possible to set up to two different
speed ranges that the ACS 140 will skip over.
Note! When the PID Control macro is used, critical frequencies are ignored.
Example: A fan system vibrates badly from 18 Hz to 23 Hz and from 46 Hz to
52 Hz. Set the parameters as follows:
CRIT
FREQ
1
LO
= 18 Hz and
CRIT
FREQ
1
HI
= 23 Hz
CRIT
FREQ
2
LO
= 46 Hz and
CRIT
FREQ
2
HI
= 52 Hz
Figure 7 Example of critical frequencies setting in a fan system with bad
vibrations at frequency ranges 18 Hz to 23 Hz and 46 Hz to 52 Hz.
Code Description
2501
CRIT FREQ SEL
Critical frequencies activation.
0 =
OFF
1 =
ON
2502
CRIT FREQ 1 LO
Critical frequency 1 start.
Note! If LOW > HI, no critical frequency lock-out will happen.
2503
CRIT FREQ 1 HI
Critical frequency 1 end.
2504
CRIT FREQ 2 LO
Critical frequency 2 start.
2505
CRIT FREQ 2 HI
Critical frequency 2 end.
Note! If LOW > HI, no critical frequency lock-out will happen.
f
output
[Hz]
f
REF
[Hz]
f1L
18
f1H
23
f2L
46
f2H
52
52
46
23
18