364xS User’s Manual
18
Installation
Wiring
HART hand-held communicator may be connected at any wiring termination point in the loop, provided the
minimum resistance is 250 ohm. If this is less than 250 ohm, additional resistance should be added to allow
communications.
Wiring requirements
For signal / power connection use twisted, stranded pairs of wiring no 18 to 22 AWG / 0.8 to 0.35 mm
2
Ø up
to 5,000 feet (1 500 meters). Longer loops require larger wire.
If a shielded wire is used the shield should be grounded only at one end, not both ends. In case of wiring at
transmitter end, use the terminal located inside the housing marked with the symbol:
Protective Earthing
Wire this ground connection marked with the symbol to a suitable earth ground.
For a transmitter measuring loop an earth ground should maintain a resistance of 5 ohms or less.
Use a heavy conductor, at least 15 AWG / 1,6 mm
2
Ø
WARNING !
A protective grounding connection is absolutely necessary to insure personnel protection, to protect against
surge and to prevent explosions in potentially explosive atmosphere.
WARNING !
The surge protection is always present and if the transmitter is installed in a Hazardous classified location, it
must be powered from a voltage source isolated from mains (galvanic separation). Furthermore the potential
equalization for the entire powering cable must be guaranteed since the intrinsic safety circuit of the
transmitter is grounded.
Hazardous
(Classified)
Location
Unclassified
Hazardous
Location
Содержание 2600T Pressure Transmitter Series
Страница 1: ...InstrumentationIT 2600T Pressure Transmitter family ABB User s Manual 364DS and 364PS Models ...
Страница 7: ...364xS User s Manual 7 This page has been intentionally left blank ...
Страница 72: ...364xS User s Manual 72 Additional Safety ...
Страница 74: ...364xS User s Manual 74 Additional Safety ...
Страница 75: ...364xS User s Manual 75 Digital LCD Display Keys sequences Annex I Digital LCD Integral Display Menu Flow Chart ...