364xS User’s Manual
37
Configuration
Fixed output current by Digital LCD Integral Display
To set 4 mA fixed output current
Navigate the Digital LCD Integral Display menu, select
Diagnostics
>
Loop Test
>
Set 4 mA.
Confirm.
)
Digital LCD Integral Display Keys sequence to set 4 mA fixed output current: 7 – 2 – 1
To set 20 mA fixed output current
Navigate the Digital LCD Integral Display menu, select
Diagnostics
>
Loop Test
>
Set 20 mA
for 20 mA
fixed output current. Confirm.
)
Digital LCD Integral Display Keys sequence to set 20 mA fixed output current: 7 – 2 – 2
To set any fixed output current
Navigate the Digital LCD Integral Display menu, select
Diagnostics
>
Loop Test
>
Set Custom Value
and
the fixed output current values will be available. Select the desired value and confirm.
)
Digital LCD Integral Display Keys sequence to set any fixed output current: 7 – 2 – 3
Fixed output current by CoMeter
Set of the Fixed output current by CoMeter is available with the 695 Field Indicator. Please refer to the
device manual for the appropriate operations.
Fixed output current by HHT
Set of the Fixed output current by Hand Held Terminal is available. Please refer to the device manual for the
appropriate operations.
Fixed output current by PC
Set of the Fixed output current by PC is available using dedicated Software. ABB can provide the references
and the Software. Please refer to the Software instructions for the appropriate operations.
Hardware settings
Write protect mode
Changes can be prevented to the transmitter configuration data with the write protection electronics dip
switch 2. If the transmitter write protection is activated the transmitter will not accept any writes to its
memory. Configuration changes, such as trim and reranging cannot take place. In case the Digital LCD
Integral Display is installed (no access to switch), the Write protect mode can also be set by HART command
using the HHT and the PC. Please refer to the device manual and Software instruction for the right
operation.
Position the right dip switch in ON to prevent accidental or deliberate
change of configuration data.
Position the right dip switch in OFF to change the configuration data. If
data configuration is not allowed check the Software Write lock using
the HHT or PC.
Change the failsafe direction
The transmitter alarm direction is set by repositioning the electronics dip switch 1. The output value is in
accordance with NE43 NAMUR recommendations.
ON
OFF
ON
OFF
Содержание 2600T Pressure Transmitter Series
Страница 1: ...InstrumentationIT 2600T Pressure Transmitter family ABB User s Manual 364DS and 364PS Models ...
Страница 7: ...364xS User s Manual 7 This page has been intentionally left blank ...
Страница 72: ...364xS User s Manual 72 Additional Safety ...
Страница 74: ...364xS User s Manual 74 Additional Safety ...
Страница 75: ...364xS User s Manual 75 Digital LCD Display Keys sequences Annex I Digital LCD Integral Display Menu Flow Chart ...