364xS User’s Manual
24
Configuration
HART Configuration
Basic Configuration Functions
This chapter describes some additional functions provided by the 364xS models which are unique to the
2600T pressure transmitter family.
Set the Pressure Polarity
When a pressure polarity different from default value (P2 – P1) is needed, it is possible to change it following
one of the methods described in the next paragraphs.
Caution
In case the Pressure Polarity is changed and the Range Value (LRV or URV) is different from the Range
Limit (LRL or URL) it is recommended to trim the 364XS sensor with pressure to obtain the maximum
accuracy (see the relevant paragraph in this User’s Manual).
Set the Pressure Polarity by Digital LCD Integral Display
Navigate the Digital LCD Integral Display menu, select
Device Config
>
Pressure Polarity
, and the used
High Pressure side is indicated. To change it select
Edit
then scroll the desired High Pressure side (see the
following table) with the up and down keys and confirm with
OK
.
P2 = High pressure
the high pressure side is the pressure chamber indicated as P2 on
the transmitter body. The output pressure will be P2 – P1
P1 = High pressure
the high pressure side is the pressure chamber indicated as P1 on
the transmitter body. The output pressure will be P1 – P2
)
Digital LCD Integral Display Keys sequence to set the Pressure Polarity: 2 – 5 – Edit
Set the Pressure Polarity by HHT
Changing the Pressure Polarity by Hand Held Terminal (HHT) is available. Please refer to the device manual
for the appropriated operations.
Set the Pressure polarity by PC
Changing the Pressure Polarity by PC is available using dedicated Software. ABB can provide the
references and the Software. Please refer to the Software instructions for the appropriate operations.
Set the Damping
When damping different from default value is needed, it is possible to set its value in seconds following one
of the methods described in the next paragraphs.
Set the Damping configuration by Digital LCD Integral Display
Navigate the Digital LCD Integral Display menu, select
Device Config
>
Damping
, set the desired value with
the up and down keys and confirm with
OK.
)
Digital LCD Integral Display Keys sequence to set the Damping: 2 – 3
Set the Damping configuration by CoMeter
Damping configuration by CoMeter is available with the 695 Field Indicator. Please refer to the device
manual for the appropriate operations.
Set the Damping configuration by HHT
Damping configuration by Hand Held Terminal is available. Please refer to the device manual for the
appropriate operations.
Содержание 2600T Pressure Transmitter Series
Страница 1: ...InstrumentationIT 2600T Pressure Transmitter family ABB User s Manual 364DS and 364PS Models ...
Страница 7: ...364xS User s Manual 7 This page has been intentionally left blank ...
Страница 72: ...364xS User s Manual 72 Additional Safety ...
Страница 74: ...364xS User s Manual 74 Additional Safety ...
Страница 75: ...364xS User s Manual 75 Digital LCD Display Keys sequences Annex I Digital LCD Integral Display Menu Flow Chart ...