364xS User’s Manual
39
Configuration
To set Fail Low current
Navigate the Digital LCD Integral Display menu, select
Device config
>
Output on alarm
>
Set Fail Current
>
Fail Low
>
Edit
,
and the value change will be possible. Select the desired value and confirm.
)
Digital LCD Integral Display Keys sequence to set the Fail Low current: 2 – 4 – 2 – 4 - Edit
Set the Current Output limits by HHT
The setting of the Current Output limits by Hand Held Terminal is available. Please refer to the device
manual for the right operations.
Set the Current Output limits by PC
The setting of the Current Output limits by PC is available using dedicated Software. ABB can provide the
references and the Software. Please refer to the Software instructions for the right operations.