364xS User’s Manual
23
Configuration
Define the Lower Range value (LRV)
If the desired LRV is different from the indicated select
Edit
, scroll the desired value for the digit in reverse
color with the up and down keys and confirm with
Next.
Repeat the operation for the seven digits and
confirm with
OK.
Select
Next
to continue.
Note: the minimum and the maximum allowed values are indicated on the display.
Define the Upper Range Value (URV)
If the desired URV is different from the indicated select
Edit
, scroll the desired value for the digit in reverse
color with the up and down keys and confirm with
Next.
Repeat the operation for the seven digits and
confirm with
OK.
Select
Next
to continue.
Note: the minimum and the maximum allowed values are indicated on the display.
Define the Transfer Function Type
If the desired Tranfer Function is different from the indicated select
Edit
then scroll the desired Transfer
Function (see the following table) with the up and down keys and confirm with
OK
. Select
Next
to continue.
Linear
Output = x
Square Root
Output = x
1/2
3/2
Output = x
3/2
5/2
Output = x
5/2
Polynomial
Output = A
0
+ A
1
x + A
2
x
2
+ A
3
x
3
+ A
4
x
4
+ A
5
x
5
Double Poly
Output = B
0
+ B
1
x + B
2
x
2
if
x
≤
k
Output = C
0
+ C
1
x + C
2
x
2
if
x
>
k
Bidirectional Flow
Define the Linearization Point
If the desired Linearization Point for the Square Root Transfer Function is different from the indicated select
Edit,
scroll the desired value for the digit in reverse colour with the up and down keys and confirm with
Next.
Repeat the operation for the five digits and confirm with
OK.
Select
Next
to continue.
Note: the minimum and the maximum values to introduce is indicated on the display.
Define the Low Flow Cut Off
If the desired Low Flow Cut Off for a Flow Transfer Function is different from the indicated select
Edit,
scroll
the desired value for the digit in reverse colour with the up and down keys and confirm with
Next.
Repeat the
operation for the five digits and confirm with
OK.
Select
Next
to continue.
Note: the minimum and the maximum values to introduce is indicated on the display.
Run the Zero Scaling
In case a Zero Scaling is required apply the pressure for the Zero and select
OK
. Wait for the auto-set end
(the bargraph will indicate the working progress). Select
Next
to continue.
Define the Damping
If the desired Damping is different from the indicated value change it with the up and down keys and confirm
with
OK.
Содержание 2600T Pressure Transmitter Series
Страница 1: ...InstrumentationIT 2600T Pressure Transmitter family ABB User s Manual 364DS and 364PS Models ...
Страница 7: ...364xS User s Manual 7 This page has been intentionally left blank ...
Страница 72: ...364xS User s Manual 72 Additional Safety ...
Страница 74: ...364xS User s Manual 74 Additional Safety ...
Страница 75: ...364xS User s Manual 75 Digital LCD Display Keys sequences Annex I Digital LCD Integral Display Menu Flow Chart ...