Advant Controller AC 31 / Issued: 01.99
3 – 19
Technical specifications
3
3.6.2
Technical specifications of the analog central extension
The analog extensions are powered at 5 V and 24 V d.c. by the basic unit or extensible remote
unit to which they are connected.
The analog value with a customised format of each channel is displayed on a 4 digit display.
The channel number is selected by the push button on the front side.
Warning: the extensions must not be connected or disconnected under power supply.
XM 06 B5
XE 08 B5
XTC 08
- Number of analog inputs
4
8
-
- Number of analog outputs
2
-
-
- Number of displayed internal values
-
8
- Display values - Range
+/- 9999
+/- 9999
+/- 9999
- Filtering of 50/60 Hz
yes
yes
- Minimum acquisition time
80 ms
160 ms
- Transfer time of the analog I/O
120 ms/10 ms
200 ms
- Maximum power dissipation
3 W
3 W
- Weight
200 g
200 g
150 g
Analog inputs
Voltage
Current
Pt 100
Pt 1000
- Nominal range:
- Maximum values
+/- 10 V
+/- 30 V
0…20 mA
4…20 mA
+/- 25 mA
- 200 °C
+ 450 °C
- 200 °C
+ 450 °C
- Isolated inputs (test voltage)
- Resolution
500 V
12 bits + sign
500 V
12 bits
500 V
500 V
- Min resolution at input (
±
1 LSB)
- Full scale precision
+/- 2.5 mV
≤
+/- 0.7 %
+/- 5 µA
≤
+/- 0.8 %
+/- 0.1 °C
≤
+/- 1.5 °C
+/- 0.1 °C
≤
+/- 1.5 °C
- Word value range read by the
basic unit
+/- 32767
0…32767
- 2000/+4500 - 2000/+4500
in preparation
- Amplification error between two
channels
70 dB
70 dB
70 dB
70 dB
- Input impedance
100 k
Ω
100
Ω
100 k
Ω
100 k
Ω
- Sensor tolerance:
Type A (IEC 751)
Type B (IEC 751)
- Linearization for
Pt 100/Pt 1000 probe
yes
yes
yes
yes
- Temperature coefficient
100 ppm
100 ppm
100 ppm
100 ppm
- Dissipation sensor:
0 °C
450 °C
0.625 mW
1.6 mW
0.0625 mW
0.16 mW
- Filtering time by input
10 ms
10 ms
10 ms
10 ms
- Diagnosis
no
no
no
no
- Cable length:
shielded
short-circuited unused channels
50 m
yes
yes
50 m
yes
yes
50 m
yes
yes
50 m
yes
yes
Содержание 07AC91
Страница 6: ...Contents 4 Advant Controller AC 31 Issued 08 99 3 ...
Страница 58: ...Installation 4 10 Advant Controller AC 31 Issued 08 99 3 Figure 16 Relay outputs Figure 17 Transistor outputs ...
Страница 62: ...Installation 4 14 Advant Controller AC 31 Issued 08 99 3 Figure 22 Extension XK 08 F1 l ...
Страница 94: ...Programming 5 22 Advant Controller AC 31 Issued 01 99 3 ...
Страница 110: ...Communication 6 16 Advant Controller AC 31 Issued 01 99 3 ...
Страница 122: ...Appendix A 4 Advant Controller AC 31 Issued 08 99 3 ...
Страница 123: ......