Advant Controller AC 31 / Issued: 01.99
6 – 15
Communication
3
Commands (Connection elements) for creating the user program
Command
Function
AEND
Prepare a programming change on a running PLC program
ALT
Reactivate the user program stored in EEPROM
AL
Display capacity utilization of basic unit, usually less than 100 %
D
Display program
DEEP
Erase PLC program in EEPROM
FREI
Enable a program change to a running PLC program
IDA
Display program identification
IDR
Delete program identification
IDS
Enter program identification
K
Enter/edit values of indirect constants such as Kx,x, KWx,x, KDx,x
NOP
Delete program part, i.e. overwrite program part with NOPs
O
Optimize the program, all NOPs are deleted, syntax: O<CR>
P
Display free program memory area
S
Enter/edit PLC program (substitute)
SP
Save PLC program in EEPROM
V
Move user program (only towards the end)
Commands for testing the user program
Command
Function
A
Abort user program
FEHLER
Display contents of the error register
FORC
Enter force values (max. 7 word and 31 bits)
FORCA
Display force value
FORCR
Delete forcing
G
Start user program
KALT
Perform cold start
PS
Display program status
ST
Display basic unit status
WARM
Perform warm start
Y
Overwrite value of a variable with a value to be entered
Z
Display status of variables
ZD
Display and continually update status of variables
ZZ
Display only the values of variables
Configuration commands
KONFS
Display/change operating modes (English/German). German has to be used
with the 907 PC 331 programming software.
PASS
Password
Enable or disable the password
Value: 4 hexadecimal numbers
The value 0000 is not allowed.
If the program is protected by a password, the user does not have access to
the following commands:
AEND, D, DEEP, FREI, N, NOP, O, S, V (display or modification of
programs).
UHR
Display time and date
UHRS
Set time and date (no syntax check)
PASS
VALUE
<CR>
Содержание 07AC91
Страница 6: ...Contents 4 Advant Controller AC 31 Issued 08 99 3 ...
Страница 58: ...Installation 4 10 Advant Controller AC 31 Issued 08 99 3 Figure 16 Relay outputs Figure 17 Transistor outputs ...
Страница 62: ...Installation 4 14 Advant Controller AC 31 Issued 08 99 3 Figure 22 Extension XK 08 F1 l ...
Страница 94: ...Programming 5 22 Advant Controller AC 31 Issued 01 99 3 ...
Страница 110: ...Communication 6 16 Advant Controller AC 31 Issued 01 99 3 ...
Страница 122: ...Appendix A 4 Advant Controller AC 31 Issued 08 99 3 ...
Страница 123: ......