Technical specifications
3 – 20
Advant Controller AC 31 / Issued: 01.99
3
Technical specifications of the analog central extension, continued
XM 06 B5
Analog outputs
Voltage
Current
- Nominal range
- Max. current
+/- 10 V
2 mA
0…20 mA
4…20 mA
20 mA
- Isolation of the outputs/electronic
- Resolution
500 V
11 bits + sign
500 V
12 bits
- Min output resolution (
±
1 LSB)
+/- 5 mV
+/- 5 µA
- Word value range
+/- 32767
0… 32767
- Linearity of full range
1.2 %
1.3 %
- Max. resistance
400
Ω
- Diagnosis
no
no
- Cable length:
shielded
50 m
yes
50 m
yes
- Permissible total voltage drop at the sensors and lines circuited in series = Max 8 V
- Configuration:
Voltage
Current
- With push-button
yes
yes
- With connection elements (CE) yes (chapter 5.4 – configuration)
3.6.3
Analog inputs diagrams
Current 4-20 mA:
3.75 mA