Advant Controller AC 31 / Issued: 01.99
6 – 9
Communication
3
Variable types
Variables
MODBUS
®
addresses
as hexadecimal values
MODBUS
®
addresses
as decimal values
Digital inputs
E 00,00
E 00,01
...
E 00,15
0000
0001
...
000F
0000
0001
...
0015
E 01,00
...
E 61,15
0010
...
03DF
0016
...
0991
E 62,00
...
E 62,15
03E0
...
03EF
0992
...
1007
E 63,00
...
E 68.15
03F0
...
044F
1008
...
1103
Digital outputs
A 00,00
A 00,01
...
A 00,15
1000
1001
...
100F
4096
4097
...
4111
A 01,00
...
A 61,15
1010
...
13DF
4112
5087
A 62,00
...
A 62,15
13E0
...
13EF
5088
...
5103
A 63,00
...
A 68,15
13F0
...
144F
5104
...
5199
Bit flags
M 000,00
M 000,01
...
M 000,15
2000
2001
...
200F
8192
8193
...
8207
M 001,00
...
M 099,15
2010
...
263F
8208
...
9791
M 230,00
...
M 254,15
2E60
...
2FEF
11872
...
12271
M 255,00
...
M 255,15
2FF0
...
2FFF
12272
...
12287
Steps
S 00,00
S 00,01
...
S 00,15
3000
3001
...
300F
12288
12289
...
12303
S 01,00
...
S125,15
3010
...
37DF
12304
...
14303
Содержание 07AC91
Страница 6: ...Contents 4 Advant Controller AC 31 Issued 08 99 3 ...
Страница 58: ...Installation 4 10 Advant Controller AC 31 Issued 08 99 3 Figure 16 Relay outputs Figure 17 Transistor outputs ...
Страница 62: ...Installation 4 14 Advant Controller AC 31 Issued 08 99 3 Figure 22 Extension XK 08 F1 l ...
Страница 94: ...Programming 5 22 Advant Controller AC 31 Issued 01 99 3 ...
Страница 110: ...Communication 6 16 Advant Controller AC 31 Issued 01 99 3 ...
Страница 122: ...Appendix A 4 Advant Controller AC 31 Issued 08 99 3 ...
Страница 123: ......