Advant Controller AC 31 / Issued: 01.99
3 – 9
Technical specifications
3
40 series
50 series
07 CR 41
24 V d.c.
07 CT 41
24 V d.c.
07 CR 41
120/230 V
a.c.
07 KR 51
24 V d.c.
07 KT 51
24 V d.c.
07 KR 51
120/230 V
a.c.
Integrrated outputs
- Number of outputs
6 Relays
6 Transistor
6 Relays
6 Relays
6 Transistor
6 Relays
- Isolated outputs/electronic
1500 Vrms
1 min
1500 V a.c.
1500 Vrms
1 min
1500 Vrms
1 min
1500 V a.c.
1500 Vrms
1 min
- Output current/channel at
24 V d.c.
- Output current/channel at
24 V d.c
230 V a.c.:
2 A
2 A AC-1
0.5 A AC-15
0.5 A
1 A for
A62,00 and
A62,01
-
2 A
2 A AC-1
0.5 A AC-15
2 A
2 A AC-1
0.5 A AC -15
0.5 A
1 A for
A62,00 and
A62,01
-
2 A
2 A AC-1
0.5 A AC-15
- Total load current
6 x 2 A
4 x 0.5 A
+ 2 x 1 A
6 x 2 A
6 x 2 A
4 x 0.5 A
+ 2 x 1 A
6 x 2 A
- Output leakage current
-
< 200
µ
A
-
-
< 200
µ
A
-
- Leakage voltage
-
0.5 V at
max. 500 mA
-
-
0.5 V at
max. 500 mA
-
- Minimum load
10 mA under
12 V d.c.
12 V
10 mA under
12 V d.c.
10 mA under
12 V d.c.
12V
10 mA under
12 V d.c.
- Breaking capacity under 120 V a.c.
(contact rating code B300)
(UL)
2 A
2 A
2 A
2 A
- Breaking capacity under 250 V a.c.
(contact rating code B300)
(UL)
2 A (1.5 A
acc. to
UL)
2 A (1.5 A
acc. to
UL)
2 A (1.5 A
acc. to
UL)
2 A (1.5 A
acc. to
UL)
- Number of groups
2 (2+4)
2 (2+4)
2 (2+4)
2 (2+4)
- Switching frequency:
for resistive loads
for inductive loads
for lamps
< 1 Hz
< 0.2 Hz
< 0.2 Hz
5 kHz
< 1 Hz
< 0.2 Hz
< 0.2 Hz
< 1 Hz
< 0.2 Hz
< 0.2 Hz
5 kHz
< 1 Hz
< 0.2 Hz
< 0.2 Hz
- Maximum number of switches:
for AC-1
for AC-15
1 million
100.000
-
-
1 million
100.000
1 million
100.000
-
-
1 million
100.000
- Short circuit and overload
protection
external
thermic
external
external
thermic
external
- Surge voltage protection
external
yes
external
external
yes
external
- Outputs diagnosis
no
overload and
short circuit
no
no
overload and
short circuit
no
- Cable length:
unshielded
shielded
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m
Содержание 07AC91
Страница 6: ...Contents 4 Advant Controller AC 31 Issued 08 99 3 ...
Страница 58: ...Installation 4 10 Advant Controller AC 31 Issued 08 99 3 Figure 16 Relay outputs Figure 17 Transistor outputs ...
Страница 62: ...Installation 4 14 Advant Controller AC 31 Issued 08 99 3 Figure 22 Extension XK 08 F1 l ...
Страница 94: ...Programming 5 22 Advant Controller AC 31 Issued 01 99 3 ...
Страница 110: ...Communication 6 16 Advant Controller AC 31 Issued 01 99 3 ...
Страница 122: ...Appendix A 4 Advant Controller AC 31 Issued 08 99 3 ...
Страница 123: ......