Programming
5 – 14
Advant Controller AC 31 / Issued: 01.99
3
•
Starting up the CS31 system after power ON, warm or cold start
(only 50 series)
Õ
Absolute identifier:
KW 00,09
Õ
Symbolic identifier:
HOCHFAHR
Õ
This system constant only takes effect if the basic unit is configured as the bus master.
Õ
Meaning of the value of the constants:
The user program is started.
The basic unit does not take any notice of whether the remote units are initialized and
adopted into the CS31 bus cycle: =0
The user program is not started until at least
n remote modules have been initialized and adopted into the CS31 bus cycle: =+n
Õ
Range of values:
0...+31
Õ
Default value:
0
i.e. user programs are started immediately.
Changes to these system constants take effect:
Õ
on the next warm start or
Õ
on the next cold start
•
Size of the transmitting area of the slave basic unit
Õ
Absolute identifier:
KW 00,10
Õ
Symbolic identifier:
SLV_SEND
Õ
Meaning of the value of the constants:
The slave basic unit can be used
either in the digital area or word area at the CS31 system
bus. The digital values are transferred byte by byte. It is possible to set the number of bytes
(or words) which are to be sent from the slave basic unit to the master basic unit.
Õ
For use in the digital area:
Transmitting: 2...15 bytes
2...15
Õ
For use in the word area:
Transmitting: 1...8 words
101...108
Õ
Default value:
4
Õ
Range of values:
2...15 and 101...108
Changes to these system constants take effect:
Õ
on the next warm start or
Õ
on the next cold start
Note:
The default setting is
-
Digital area with:
-
transmit 4 bytes and
-
receive 4 bytes.
This is defined by the default combination
KW 00,10 = KW 00,11 = 0.
The configured combination
KW 00,10 = KW 00,11 = 4
has the same result as the default combination.
The combination:
KW 00,10 = KW 00,11 = 100.
Is not allowed (It would mean transmit 0 words and receive 0 words)
Õ
Changing the system constants takes effect immediately.
Содержание 07AC91
Страница 6: ...Contents 4 Advant Controller AC 31 Issued 08 99 3 ...
Страница 58: ...Installation 4 10 Advant Controller AC 31 Issued 08 99 3 Figure 16 Relay outputs Figure 17 Transistor outputs ...
Страница 62: ...Installation 4 14 Advant Controller AC 31 Issued 08 99 3 Figure 22 Extension XK 08 F1 l ...
Страница 94: ...Programming 5 22 Advant Controller AC 31 Issued 01 99 3 ...
Страница 110: ...Communication 6 16 Advant Controller AC 31 Issued 01 99 3 ...
Страница 122: ...Appendix A 4 Advant Controller AC 31 Issued 08 99 3 ...
Страница 123: ......