92
Configuration
Manual Corrigo E Ventilation, revision Q
Start step 1: 10 %
Stop step 1: 5 %
Start step 2: 45 %
Stop step 2: 40 %
Start step 3: 70 %
Stop step 3: 65 %
Start step 4: 95 %
Stop step 4: 90 %
Control parameters. Heater groups is used to calculate activation levels for binary control.
"Hyst." is the switching differential used for each step when running binary control.
Heater groups: 4
Minimum on/off-
time: 60 sec
Hyst.: 0.5 %
16.24.2 Step controller cooling
"Step controller Cooling" can be set to sequential or binary.
Step contr. cooling
Sequential
"Step controller Cooling" activation levels for sequential control.
For binary control the activation levels are calculated by the controller depending on the
number of steps involved
Start step 1: 10 %
Stop step 1: 5 %
Start step 2: 50 %
Stop step 2: 45 %
Start step 3: 95 %
Stop step 3: 90 %
Control parameters. Chiller groups is used to calculate activation levels for binary control.
“Hyst.” is the switching differential used for each step when running binary control.
Chiller groups: 3
Minimum on/off-
time: 60 sec
Hyst.: 0.5 %
When DX cooling is used in conjunction with pressure controlled or flow controlled fans it
is possible to block DX cooling if the supply air fan control signal falls below a preset
values. The blocking level is individually settable for each DX cooling step.
At lower SAF-output
block step 1: 0 %
block step 2: 0 %
block step 3: 0 %
For a more detailed description, see section 5.1.4 Step controllers.
Содержание Corrigo E15D-S-LON
Страница 1: ...Corrigo E manual Ventilation application Copyright AB Regin Sweden 2013 ...
Страница 5: ...APPENDIX FREQUENCY CONVERTERS 117 ...
Страница 13: ...Manual Corrigo E Ventilation revision Q About Corrigo E 13 Position of the terminals on Corrigo E ...
Страница 28: ...28 Commissioning Manual Corrigo E Ventilation revision Q Other functions Chapter 18 Alarm handling etc ...
Страница 116: ...Appendix ...