106
Expansion model
Manual Corrigo E Ventilation, revision Q
Chapter 17 Expansion model
There are eight different 2-port Corrigo models with 15/28 inputs/outputs, with or without display,
and with or without TCP/IP port. For a list of the different models, see the Corrigo E model
overview in chapter 2.
17.1 Port 1
On a 2-port Corrigo, port one is used for connection to E tool
©
and possibly a SCADA system. On
an Exx2S-WEB model, port 1 is the TCP/IP output.
17.2 Port 2
Port 2 is used for expansion units, e.g. expansion units and the Vacon NXL/Lenze
SMV/Omron/Emerson frequency converters. A maximum of two frequency converters and two
expansion units can be connected. If set as slave, port 2 can also be used with E tool
©
. The
controllers must be of the type Corrigo E. There is no point in utilising slave units with display since
the display cannot be used or show anything. However, an external display is required when starting
up slave controllers without display for the first time (if the configuration is not done via E tool
©
).
All configuration takes place either via E tool
©
or via the display on the master controller. All inputs
and outputs can be viewed in the master controller. For configuration of port 2, see section 16.27.2.
From version 3.1, frequency converters and expansion units can be used together, connected to port
2.
17.3 Wiring
17.3.1 Vacon/Lenze/Omron/Emerson/LS/EBM frequency
converters
If the Corrigo is intended to control of one or two of the Vacon NXL/Lenze SMV/Omron
V1000/Emerson frequency converters, Modbus communication via port two is utilised.
For additional settings for frequency converters, see appendix at the end of this document.
17.3.2 Expansion units EXOline
Communication between the master and expansion units takes place via EXOline. The slave
controllers will be given the addresses 241:1 and 241:2 (ELA:PLA) respectively.
Содержание Corrigo E15D-S-LON
Страница 1: ...Corrigo E manual Ventilation application Copyright AB Regin Sweden 2013 ...
Страница 5: ...APPENDIX FREQUENCY CONVERTERS 117 ...
Страница 13: ...Manual Corrigo E Ventilation revision Q About Corrigo E 13 Position of the terminals on Corrigo E ...
Страница 28: ...28 Commissioning Manual Corrigo E Ventilation revision Q Other functions Chapter 18 Alarm handling etc ...
Страница 116: ...Appendix ...