Manual Corrigo E Ventilation, revision Q
Temperature
63
Setpoint
Control mode 8: Outdoor temperature compensated extract air control.
Extract air temp
Actual: 21.0°C
Setp.: 21.1°C
Outdoor comp. setp.
-20.0°C = 25.0°C
-15.0°C = 24.0°C
-10.0°C = 23.0°C
Outdoor comp. setp.
-5.0°C = 23.0°C
0.0°C = 22.0°C
5.0°C = 20.0°C
Outdoor comp. setp.
10.0°C = 18.0°C
15.0°C = 18.0°C
If cascade control
max/min supply setp.
Max: 30.0°C
Min: 12.0°C
In control mode 8, the extract air setpoint is compensated based on outdoor temperature. Note that
the curve must be adjusted for optimal functionality.
Both the outdoor and extract air temperature are changeable for the curve.
Support control heating
Support heating
Room temp for
Start: 15.0°C
Stop: 21.0°C
Support control cooling
Support cooling
Room temp for
Start: 30.0°C
Stop: 28.0°C
Frost protection temperature
Frost protection
Actual: 30.9°C
De-icing exchanger
De-icing exchanger
Actual: 11.2°C
Setpoint: -3.0°C
Hysteresis: 1.0°C