Manual Corrigo E Ventilation, revision Q
Configuration
89
16.15 Humidity control
Humidity control can be configured as either humidification or dehumidification or as combined
humidification/dehumidification.
These settings are for the digital output "Humidification/Dehumidification".
Humidity control
Humid-/Dehumidificat
Start limit: 15%
Stop limit: 5%
For a detailed description, see the section Humidity control.
16.16 Exchanger de-icing
Exchanger de-icing
Yes
De-icing parameters
Setp.De-icing:-3.0°C
Hysteresis: 1.0 °C
Stoptemp SAF:-10.0°C
Min. run time: 5 min
For detailed description of exchanger alternatives, see section 5.1.3 Heat exchanger.
16.17 Cooling recovery
Cooling recovery
Off
Cooling limit: 0.0°C
Cooling limit is the difference in temperature between extract air and outdoor air.
For details, see section 5.1.7 Cooling recovery.
16.18 Minimum limit dampers
Min limit dampers
Not active
Min limit.: 5%
For detailed description of exchanger alternatives, see section 5.1.3 Heat exchanger.
16.19 Enthalpy control
Cooling recovery
run when enthalpy is
greater outdoor than
indoor : Active
For a detailed description, see section 5.1.8 Enthalpy control.
16.20 External setpoint
An external setpoint device, for example TBI-PT1000 or TG-R4/PT1000 can be connected. The
setpoint device must follow the PT1000 resistance curve. The setting range can be restricted.
Содержание Corrigo E15D-S-LON
Страница 1: ...Corrigo E manual Ventilation application Copyright AB Regin Sweden 2013 ...
Страница 5: ...APPENDIX FREQUENCY CONVERTERS 117 ...
Страница 13: ...Manual Corrigo E Ventilation revision Q About Corrigo E 13 Position of the terminals on Corrigo E ...
Страница 28: ...28 Commissioning Manual Corrigo E Ventilation revision Q Other functions Chapter 18 Alarm handling etc ...
Страница 116: ...Appendix ...