Manual Corrigo E Ventilation, revision Q
Functional description
29
Chapter 5 Functional description
5.1 Temperature control
General
Corrigo E has a choice of the following control modes:
1.
Supply air control
2.
Outdoor temperature compensated supply air control
3.
Cascaded room temperature control
4.
Cascade connected extract air temperature control
5.
Outdoor temperature dependent switching between supply air control and room
temperature control
6.
Outdoor temperature dependent switching between supply air control and extract air
control
7.
Outdoor compensated room temperature control
8.
Outdoor compensated extract air control
The supply air temperature controller is reverse acting, i. e. the output will increase for decreasing
temperature. The controller is a PI-controller with settable P-band and I-time.
In the first two modes the supply air temperature will be controlled using the supply air temperature
and the user setpoint values as control inputs.
In modes three and four the supply air is controlled as part of a cascade controller together with the
room/extract temperature controller. The room/extract temperature offset will dictate the supply air
temperature setpoint.
Mode five and six vary according to the outdoor temperature: Supply air control in winter and
cascaded room control or cascaded extract air control in summer.
In applications with mixing dampers instead of heat exchanger the signal for the damper control will
be reversed compared to the signal for heat exchanger control i. e. decreasing signal on increasing
heat demand. This is done automatically on configuring the exchanger output = dampers.
The heater can be either a hot water heater battery or an electric heater.
Outputs
The supply air controller output is split between one or more of the output blocks "Heating Y1",
"Exchanger Y2" and "Cooling Y3". Each of these output blocks can be bound to either an analogue
0…10 V DC output or to two digital 3-position increase/decrease outputs.
Each output block has two parameters for setting the control range:
Heating Controller Output signal (HCOut) at which the output should be 0 %
Heating Controller Output signal (HCOut) at which the output should be 100 %
These settings are used to establish the output activation order and to split the P-band between the
outputs.
Содержание Corrigo E15D-S-LON
Страница 1: ...Corrigo E manual Ventilation application Copyright AB Regin Sweden 2013 ...
Страница 5: ...APPENDIX FREQUENCY CONVERTERS 117 ...
Страница 13: ...Manual Corrigo E Ventilation revision Q About Corrigo E 13 Position of the terminals on Corrigo E ...
Страница 28: ...28 Commissioning Manual Corrigo E Ventilation revision Q Other functions Chapter 18 Alarm handling etc ...
Страница 116: ...Appendix ...