22
Installation and wiring
Manual Corrigo E Ventilation, revision Q
Wiring diagram Corrigo E15-S
(default in- and output configuration)
1
G
Supply voltage 24 V AC or 24 V DC,
±15%. 50/60 Hz
50
B
RS485 EXOline / Modbus (not in
WEB (TCP/IP) models)
2
G0
51
A
3
Protective earth
52
N
4
+C
+24 V DC. Reference for digital inputs DI.
53
E
10
G
DO
Reference for digital outputs DO.
57
Net+
LON-connection (LON-versions only)
11
DO1
Start/stop supply air fan (SAF) 1/1-speed
58
Net-
12
DO2
Start/stop extract air fan (EAF) 1/1-speed
59
Egnd
13
DO3
Start/stop Circulation pump, Heating
14
DO4
Sum alarm A + B
71
DI1
Run indication / Motor protection SAF
72
DI2
Run indication / Motor protection EAF
30
Agnd
Reference pole for analogue inputs AI
73
DI3
Run indication /alarm, Circ. pump Heating
31
AI1
Outdoor temperature sensor
74
DI4
Extended running
32
AI2
Supply air temperature sensor
33
Agnd
Reference pole for analogue inputs AI
90
Agnd
Reference pole for analogue outputs AO
34
AI3
Frost protection sensor
91
AO1
Y1 Actuator Heating
35
AI4
Room temperature sensor 1
92
AO2
Y2 Actuator Exchanger
93
AO3
Y3 Actuator Cooling
Wiring diagram Corrigo E8-S
(default in- and output configuration)
1
G
Supply voltage 24 V AC or 24 V DC,
±15%. 50/60 Hz
50
B
RS485 EXOline / Modbus (not in
WEB (TCP/IP) models)
2
G0
51
A
3
Protective earth
52
N
4
+C
+24 V DC. Reference for digital inputs DI.
53
E
10
G
DO
Reference for digital outputs DO.
57
Net+
LON-connection (LON-versions only)
11
DO1
Start/stop supply air fan (SAF) 1/1-speed
58
Net-
12
DO2
Start/stop Circulation pump, Heating
59
Egnd
30
Agnd
Reference pole for analogue inputs AI
71
DI1
Run indication / Motor protection SAF
31
AI1
Outdoor temperature sensor
72
DI2
Run indication /alarm, Circ. pump Heating
32
AI2
Supply air temperature sensor
73
DI3
High temp. limit switch / Frost prot. thermostat
90
Agnd
Reference pole for analogue outputs AO
91
AO1
Y1 Actuator Heating
Содержание Corrigo E15D-S-LON
Страница 1: ...Corrigo E manual Ventilation application Copyright AB Regin Sweden 2013 ...
Страница 5: ...APPENDIX FREQUENCY CONVERTERS 117 ...
Страница 13: ...Manual Corrigo E Ventilation revision Q About Corrigo E 13 Position of the terminals on Corrigo E ...
Страница 28: ...28 Commissioning Manual Corrigo E Ventilation revision Q Other functions Chapter 18 Alarm handling etc ...
Страница 116: ...Appendix ...