48
Functional description
Manual Corrigo E Ventilation, revision Q
When the function is activated and combined with pressure controlled fans and the CO
2
/VOC-value
rises above control value one the fans will start at reduced speed, if they are not already running.
Should the CO
2
/VOC-value continue to rise the fan speed will also increase until the CO
2
/VOC-
value reaches control value two at which point the fans will be running at normal speed. The fans
will stop when the CO
2
/VOC-value falls 160 ppm below control value one.
When used with 2-speed fans they will start using reduced speed when the CO
2
/VOC-value rises
above control value one and switch to normal speed when the CO
2
/VOC-value reaches control
value two. The fans will stop when the CO
2
/VOC-value falls 160 ppm below control value one.
If demand controlled ventilation is activated in combination with mixing dampers, and the CO
2
-
value rises above the setpoint value, the dampers will let in more outdoor air. The function is
controlled by a PI-controller. See section 5.1.3 Heat exchanger types.