Manual Corrigo E Ventilation, revision Q
Time settings
69
Chapter 13 Time settings
General
Corrigo has a year-base clock function. This means that a week-schedule with holiday periods for a
full year can be set. The clock has an automatic summertime/wintertime change-over.
Individual schedules for each week-day plus a separate holiday setting. Up to 24 individual holiday
periods can be configured. A holiday period can be anything from one day up to 365 days. Holiday
schedules take precedence over other schedules.
Each day has up to two individual running periods. For two-speed fans and pressure controlled fans
there are daily individual schedules for normal speed and reduced speed, each with up to two
running periods.
Up to 5 digital outputs can be used as timer controlled outputs. Each with individual week-
schedules with two activation periods per day. These outputs can be used to control lighting,
doorlocks etc.
Time/Date
Timer Normal speed
Timer Reduced speed
Extended running
Timer output 1
Timer output 2
Timer output 3
Timer output 4
Timer output 5
Holidays
13.1 Time / Date
This menu shows and permits the setting of time and date.
Time is shown in 24-hour format.
Date is shown in the format YY:MM:DD.
Time: 18:21
Date: 04-08-04
Weekday: Wednesday
13.2 Timer Normal speed
There are eight separate setting menus, one for each weekday and one extra for holidays.
Holiday schedules take precedence over other schedules.
For 24 hour running, set a period to 0:00 – 24:00.
To inactivate a period, set the time to 00:00 – 00:00. If both periods of a day are set to 0:00 – 0:00,
the unit will not run at 1/1-speed that day.
Normal speed
Monday
Per 1: 07:00 – 16:00
Per.2: 00:00 - 00:00
Содержание Corrigo E15D-S-LON
Страница 1: ...Corrigo E manual Ventilation application Copyright AB Regin Sweden 2013 ...
Страница 5: ...APPENDIX FREQUENCY CONVERTERS 117 ...
Страница 13: ...Manual Corrigo E Ventilation revision Q About Corrigo E 13 Position of the terminals on Corrigo E ...
Страница 28: ...28 Commissioning Manual Corrigo E Ventilation revision Q Other functions Chapter 18 Alarm handling etc ...
Страница 116: ...Appendix ...