86
COMMAND
NAME
DESCRIPTION
No.
COMMAND SYNT
AX
Command
Argument 1
Argument 2
Argument 3
Argument 4
Response
Alarm
Events
Registers
Read/Set/Reset value of Alarm Events Registers:
Status Register: (Read/Reset)
Mask Register: (R/W)
Latch Register: (R/W)
See list of the Alarm Events below:
0 FLOW_ALARM_HIGH
0x0001
1 FLOW_ALARM_LOW 0x0002
2 FLOW_ALARM_RANGE
0x0004
3 TOT
AL1_HIT_LIMIT 0x0008
4 TOT
AL2_HIT_LIMIT 0x0010
5 PRES_ALARM_HIGH 0x0020
6 PRES_ALARM_LOW
0x0040
7 PRES_ALARM_RANGE
0x0080
8 TEMP_ALARM_HIGH
0x0100
9 TEMP_ALARM_LOW
0x0200
A TEMP_ALARM_RANGE
0x0400
B PULSE_OUT_QUEUE 0x0800
C P
ASSWORD_EVENT 0x1000
D POWER_ON_EVENT 0x2000
5
A
E
NO ARGUMENT
(read Alarm
Events status
register)
AE:<V
alue>
Example: AE:0x0
R
(reset Alarm
Events status
register to
0x0000)
AER:0x0
M
(Read/Set Alarm
Events Mask
register)
NO
ARGUMENT
(read current
settings)
AEM:0x1
<V
alue>
0x0000-0x0FFF
Set new value
NOTE: all 6
characters are
required
AEM:0x11
L
(Read/Set Alarm
Events Latch
register)
NO ARGUMENT
(read current
settings)
AEL:0x1
<V
alue>
0x0000-0x0FFF
Set new value
NOTE: all 6
characters are
required
AEL:0x11