2
5
9.18.3
Anti
‐
freezing
The
alarm
will
be
activated
when
the
outlet
water
temperature
sensor
is
less
than
4°C.
It
turns
off
when
the
temperature
becomes
higher
than
+6°C.
9.18.4
Sensors
alarm
The
alarm
will
be
activated
in
the
case
of
a
short
or
open
circuit
of
any
connected
and
enabled
sensor.
The
alarm
will
be
activated
also
when
the
temperature
becomes
higher
than
the
sensors’
upper
limit
of
100°C
or
less
than
the
lower
limit
of
‐
50°C.
9.18.5
Timeout
inverter
Supposing
the
controller
does
not
communicate
with
the
driver
board
of
the
compressor,
the
time
out
alarm
will
be
activated
in
order
to
prevent
a
system’s
control
loss.
9.18.6
ON/OFF
remote
In
case
the
unit
is
remote
controlled
by
a
remote
digital
input.
9.18.7
High
pressure
If
the
on
board
pressure
transductor
detects
a
pressure
higher
than
41
bar,
the
alarm
will
be
activated.
In
this
case
the
compressor
will
stop
immediately.
The
alarm
will
reset
when
the
pressure
decreases
under
36
bar.
9.18.8
High
pressure
flow
switch
(in
series
with
the
compressor
outlet
probe)
If
the
pressure
switch
on
the
machine
detects
a
pressure
higher
than
42
bar
the
alarm
will
be
active.
In
this
case,
the
compressor
will
be
immediately
stopped.
The
alarm
resets
when
the
pressure
drops
below
32
bar.
9.18.9
Low
pressure
If
the
on
board
pressure
transductor
detects
a
pressure
lower
than
value
set
from
the
controller
(as
a
function
of
operating
mode
and/or
of
the
model)
the
alarm
will
be
activated.
In
this
case
the
compressor
will
stop
immediately.
The
alarm
will
reset
when
the
pressure
goes
over
the
set
hysteresis.
9.19
POWER
FAILURE
After
power
supply
reset:
1. The
system
comes
back
to
the
previous
state
before
the
power
failure.
2. If
the
system
is
defrosting,
this
mode
will
be
cancelled
after
power
supply
reset.
3. All
the
running
timings
will
be
cleared
and
reset
again.
9.20
User
block
allarms
table
Error
description
Code
Compressor
Pump
Resistances
Fan
Off
remote
control
E00
OFF
OFF
OFF
OFF
Inverter
hardware
malfunctioning
E75
OFF
OFF
Compressor’s
tension
too
high
E76
OFF
OFF
Power
supply
tension
out
of
bounds
E78
OFF
OFF
Compressor
not
power
supplied
E79
OFF
OFF
Inverter
time
out
malfunctioning
E80
OFF
OFF
Inlet
water
sensor
E61
OFF
OFF
OFF
OFF
Outlet
water
sensor
E62
OFF
OFF
OFF
OFF
Compressor
inlet
sensor
E63
OFF
OFF
OFF
OFF
Compressor
exhaust
temp.
sensor
+
HP
flow
switch
E64
OFF
OFF
OFF
OFF
High
pressure
transductor
E65
OFF
OFF
OFF
OFF
Low
pressure
transductor
E66
OFF
OFF
OFF
OFF
Outdoor
battery
sensor
for
climate
adjust
E67
OFF
OFF
OFF
OFF
Sanitary
water
boiler
sensor
(opt.)
E69
OFF
OFF
OFF
OFF
Water
flow
switch
E06
OFF
OFF
OFF
OFF
High
temperature
E18
OFF
OFF
High
pressure
E01
OFF
OFF
Low
pressure
E02
OFF
OFF
Anti
‐
freezing
alarm
E05
OFF
ON
OFF
OFF
10
SHUTDOWNS
FOR
LONG
PERIODS
• Turn
off
the
unit
by
placing
the
switch
of
each
unit
to
"OFF"
position.
• Close
the
water
valves.
Содержание HPE Series
Страница 21: ......
Страница 29: ...28 ...
Страница 31: ...30 16 WATER PUMP CURVES 16 1 MODELS HPE 06 09 16 2 MODELS HPE 12 15 ...
Страница 34: ...33 19 3 HPE 12 15 IN OUT 1 M ...
Страница 35: ...34 20 WIRING DIAGRAMS 20 1 MODELS HPE 06 09 ...
Страница 36: ...35 20 2 MODEL HPE 12 ...
Страница 37: ...36 20 3 MODEL HPE 15 ...
Страница 43: ...NOTE ...
Страница 44: ...NOTE ...
Страница 45: ...NOTE ...
Страница 46: ...NOTE ...
Страница 47: ......