TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
12
04/06/22
www.atcontrols.com
IOM08139 REVISION 04
M O T O R T E M P
L I M I T :
x x x x
Motor
Temperature
Monitor
Sets temperature ranges for the motor temperature monitor connected to (P8). Below values indicate duty cycle
restriction. DEFALUT = Disabled
Disabled:
Ignores input to thermistor header (P8).
75C:
Below 75C = normal
75C to 90C = 60%
90C to 105C = 40%
Above 105C = 20%
90C:
Below 90C = normal
90C to 105C = 60%
105C to 120C = 40%
Above 120C = 20%
105C:
Below 105C = normal
105C to 120C = 60%
120C to 135C = 40%
Above 135C = 20%
3.3.
FEEDBACK CONFIG submenu
The
FEEDBACK CONFIG
menu group contains parameters associated with the position feedback signal for the actuator.
The analog feedback signal can be set and adjusted here.
F E E D B A C K
T Y P E :
x x x x
Feedback
Signal Type
Sets type of feedback signal. DEFAULT = mA
mA:
0.0 to 21.5 mA
Disabled:
When command type is set for ON-OFF
C A L I B R A T E
Z E R O
x x x x
Calibrate
Feedback Zero
Sets feedback signal zero digital count value. When selected, use [PREVIOUS ▲] or [NEXT ▼] to adjust
feedback until desired value is measured. Note, this feedback will correspond to the programmed “Calibrate Close
Pos” position in the
POSITION CONFIG
menu. If command is set for reverse action, set this value accordingly.
Value is scaled between 12 bit count of 0 and 4095 for the selected command type range. Typical values can be
found in Section 4.2.1.
C A L I B R A T E
S P A N
x x x x
Calibrate
Feedback Span
Sets feedback signal span digital count value. When selected, use [PREVIOUS ▲] or [NEXT ▼] to adjust
feedback until desired value is measured. Note, this feedback will correspond to the programmed “Calibrate Open
Pos” position in the
POSITION CONFIG
menu. If command is set for reverse action, set this value accordingly.
Value is scaled between 12 bit count of 0 and 4095 for the selected command type range. Typical values can be
found in Section 4.2.1.