background image

                                      

 

 

TMC-4 Control Card 

for Electric Actuators 

Installation & Maintenance Manual  

 
 

17 

04/06/22 

www.atcontrols.com 

IOM08139 REVISION 04 

 

4.  Setup and Calibration 

 

4.1. 

Positioning Devices 

 

4.1.1. Feedback Potentiometer (P7) 

 
A feedback potentiometer connected to header (P7) is used to 
detect the position of the actuator between the 0% to 100% 
limits for modulating and proportional control applications. The 
feedback potentiometer is typically coupled to the actuator 
output indicator shaft by a set of gears. 
 
To ensure the potentiometer remains within its limits through the 
actuator operating range, the actuator should first be moved to 
the halfway, or 50%, position. The feedback potentiometer is 
then adjusted to the midpoint of its effective electrical range. For 
example, a 1kΩ potentiometer should be adjusted to 500Ω. If 
the potentiometer jumps from one end to another within the 
actuator’s operation range, for example 0Ω to 1000Ω, the TMC4 
may not be able to position correctly. 
 
The potentiometer resistance is translated into a 12 bit count value of 0 to 4095 by the TMC4, and displayed in the 
“Calibrate Close Pos” or “Calibrate Open Pos” settings in the 

POSITION CONFIG

 submenu. When the feedback 

potentiometer is at its midpoint, the digital count value shown in either setting will be 2048, as this is the midpoint value 
between the limits of 0 and 4095.  
 
It is not critical to adjust the potentiometer to exactly 2048 at the 50% position but should be close so that the value will 
not jump between the extremes of 0 and 4095 within the operating range. Centering the potentiometer approximately 
between 1900-2200 should be sufficient for most applications. 
 
The effective electrical angle of the potentiometer, actuator rotation angle, and ratio of the feedback gears determine the 
maximum and minimum digital count values at the full open and full close positions, and the subsequent range that can be 
expected. Typical digital count values are shown below for different gearing ratios or operating angles with the 50% 
position set exactly to a value of 2048. 
 

Gear Ratio / Actuator Rotation 

Minimum 

Maximum 

Range 

1:1 / 90° 

1506 

2590 

1084 

1:1 / 180° or 2:1 / 90° 

964 

3132 

2168 

1:1 / 270° or 3:1 / 90° 

422 

3674 

3252 

 

 
Note that the maximum and minimum values could be swapped depending on the rotation direction of the potentiometer 
in relation to the rotation direction of the actuator. The TMC4 will correctly interpret the readings when positions are 
calibrated. It is also not important to fall exactly at the values shown as long as the range of operation does not permit the 
digital count value to jump from 0 to 4095, or vice versa. However, as the gear ratio or actuator rotation angle increases, 
and the range increases, the allowance for deviation is reduced.  
 
 
 
 
 
 
 
 
 
 
 

Содержание Triac TMC-4

Страница 1: ...mits expansion on the capabilities of the controller to support various communication busses or other control and interface options The TMC4 provides two main positioning options proportional or two p...

Страница 2: ...enu 12 3 4 POSITION CONFIG submenu 13 3 5 COMMS CONFIG submenu 14 3 6 AUX I O CONFIG submenu 15 3 7 SYSTEM CONFIG submenu 16 4 Setup and Calibration 17 4 1 Positioning Devices 17 4 1 1 Feedback Potent...

Страница 3: ...for the TMC4 7 Feedback Potentiometer Header P7 3 point connection header for feedback potentiometer when required for actuator control This provides positioning feedback for when operating as a prop...

Страница 4: ...ementing a setting value the value step increases in value every 6 presses for more rapid adjustment Reset the step back to 1 by pressing back in opposite direction 12 Display OLED screen to show actu...

Страница 5: ...the external brake output energizes The brake setting is currently configured exclusively for use on Triac SRX series actuators and is not configurable Care must be taken when using with other type of...

Страница 6: ...Motor CW AC version Energize clockwise motor winding DC version Switch supply voltage for clockwise operation 6 Motor CCW AC version Energize counterclockwise motor winding DC version Switch supply v...

Страница 7: ...or Electric Actuators Installation Maintenance Manual 7 04 06 22 www atcontrols com IOM08139 REVISION 04 2 2 Wiring Diagrams AC Proportional Control AC Two Position Control DC Proportional Control DC...

Страница 8: ...REVISION 04 2 3 Input Output Signal Configurations Command Type mA Sinking Externally Powered Loop Control Command Type mA Sinking 2 Wire Transmitter Control Command Type 5V and 10V Command Type Poten...

Страница 9: ...TMC 4 Control Card for Electric Actuators Installation Maintenance Manual 9 04 06 22 www atcontrols com IOM08139 REVISION 04 3 Menu...

Страница 10: ...x x x Control CMD Command signal type set in Command Type setting in COMMAND CONFIG submenu FB Feedback signal type set in Feedback Type setting in FEEDBACK CONFIG submenu T E M P E R A T M T R x x x...

Страница 11: ...for the selected command type range Typical values can be found in Section 4 2 1 C A L I B R A T E S P A N x x x x Calibrate Command Span Sets command signal span digital count value When selected pro...

Страница 12: ...mA mA 0 0 to 21 5 mA Disabled When command type is set for ON OFF C A L I B R A T E Z E R O x x x x Calibrate Feedback Zero Sets feedback signal zero digital count value When selected use PREVIOUS or...

Страница 13: ...between 12 bit count of 0 and 4095 based on the measured feedback potentiometer position There is no correct value to set to but it is recommended to fall within the range of 400 3700 C A L I B R A T...

Страница 14: ...COMMAND CONFIG submenu Modbus RTU Modbus RTU Modbus TCP Modbus TCP Profibus Profibus DP U N I T I D x x Unit ID Actuator ID address Selectable from 1 to 246 DEFAULT 1 B A U D R A T E x x x x Baud Rat...

Страница 15: ...When DI2 terminals are powered the TMC4 commands a 100 0 signal and moves to programmed 0 0 position while DI3 detects local input If operating as on off actuator it will drive to the open position li...

Страница 16: ...ount as well as setting for selecting type of motor being operated and restoring factory defaults M O T O R T Y P E x x Motor Type Displays type of motor braking based on if AC version of TMC4 or DC v...

Страница 17: ...ll be 2048 as this is the midpoint value between the limits of 0 and 4095 It is not critical to adjust the potentiometer to exactly 2048 at the 50 position but should be close so that the value will n...

Страница 18: ...ch action 4 1 3 Stop Torque Limit Switch P9 Motor travel stop or torque switches connected to header P9 are used to stop the actuator regardless of set position limits This switch input should be used...

Страница 19: ...rm e Enter Calibrate Span setting and adjust feedback signal using PREVIOUS or NEXT until desired 100 feedback is achieved and confirm Typical feedback signal values are given in 4 2 1 Command and Fee...

Страница 20: ...Y P E L i m i t S W 4 4 Communication Bus Control Calibration For when using one of the optional communication bus add on modules To change values or settings press CONFIRM so value or setting flashe...

Страница 21: ...rmistor provides a temperature dependent resistance that the TMC4 inputs into an algorithm to establish a defined duty cycle limit depending on the measured temperature As the temperature increases th...

Страница 22: ...nge feedback type Incorrect feedback calibration Recalibrate feedback zero and span External loop power being provided Remove external loop power Actuator is hunting Noisy input signal Check input sig...

Страница 23: ...ion 12 bit 4096 points Feedback Signal Out Voltage 0 to 10 8 VDC min 500 load Current 0 to 21 5 mA max 980 load Resolution 12 bit 4096 points Position Feedback Voltage 0 to 3 3 VDC Potentiometer 1k Li...

Страница 24: ...tenance of A T Controls products The user should read and understand the installation operation maintenance IOM instructions included with the product and train its employees and contractors in the sa...

Отзывы: