TMC-4 Control Card 

for Electric Actuators 

Installation & Maintenance Manual  

 
 

13 

04/06/22 

www.atcontrols.com 

IOM08139 REVISION 04 

 

3.4. 

POSITION CONFIG submenu 

 
The 

POSITION CONFIG

 menu group contains parameters associated with the positioning of the actuator. There are two 

types of positioning methods used; one using limit switches for two position operation, and the other using feedback 
potentiometer for modulating for proportional control operation.  
 
When using limit switches, the open and close limits are set using the mechanical cams and limit switches in the actuator. 
These switches should be connected to (P5) Limit Switch header. When using feedback potentiometer, the open and 
close limits are programmed in this submenu and the potentiometer should be connected to (P7) Feedback Potentiometer 
header. 
 

P O S I T I O N  
T Y P E :  
            x x x x

 

Position Type 

  Sets type of feedback used for positioning. Default is set for potentiometer positioning. 

Limit SW: 

Uses position limit switches to detect discrete end of travel position for two-position 
on/off control. “Calibrate Close” and “Calibrate Open” settings are not used. 

Potent: 

Uses potentiometer to detect position for modulating and proportional positioning 
control. Limits are determined by the “Calibrate Close” and “Calibrate Open” position 
settings. 

 

 

   

C A L I B R A T E  
C L O S E   P O S  
            x x x x

 

Calibrate Close 

Position 

  Only used with potentiometer feedback to set position limit when the CW motor output is energized to move 

actuator in clockwise direction. This position will correspond to the “zero” value set in 

COMMAND CONFIG

 

submenu. When selected, use [PREVIOUS ▲] or [NEXT ▼] to drive motor to desired close/clockwise position. If 
limit switch position type is selected, this value is not used during operation. 
 
Value is scaled between 12 bit count of 0 and 4095 based on the measured feedback potentiometer position. 
There is no “correct” value to set to, but it is recommended to fall within the range of 400-3700. 

 

   

C A L I B R A T E  
O P E N   P O S  
            x x x x

 

Calibrate Open 

Position 

  Only used with potentiometer feedback to set position limit when the CCW motor output is energized to move 

actuator in counterclockwise direction. This position will correspond to the “span” value set in 

COMMAND 

CONFIG

 submenu. When selected, use [PREVIOUS ▲] or [NEXT ▼] to drive motor to desired 

open/counterclockwise position. If limit switch position type is selected, this value is not used during operation. 
 
Value is scaled between 12 bit count of 0 and 4095 based on the measured feedback potentiometer position. 
There is no “correct” value to set to, but it is recommended to fall within the range of 400-3700. 

 

   

T R A V E L  
T I M E O U T  
              x x S

 

Travel Timeout 

  Only used with communication bus options. Value should be greater than the normal actuator travel time. The 

TMC4 begins a timer when the motor outputs are energized to control the actuator to the commanded position. If 
the timer exceeds the timeout value before the command position is reached, the motor output is turned off. When 
selected, use [PREVIOUS ▲] or [NEXT ▼] to adjust value. Can also be configured via communication protocol.  
DEFALUT = 60 seconds 

 

   

S W   A C T I N G  
L I M .   T O R Q .  
x x x x     x x x x

 

Switch Action 

  Sets contact logic of the position limit switches connected to header (P5) and stop/torque switches connected to 

(P9).  
N.O. indicates normally open action where input is activated when switch contact is closed. 
N.C. indicates normally closed action where input is activated when switch contact is opened. 
DEFAULT = N.O. / N.O. 

 
 
 

NOTE:

 Calibrate Close and Calibrate Open value is scaled between 12 bit count of 0 and 4095 based on potentiometer reading. It may 

increase or decrease depending on how potentiometer is wired, but should never jump between 0 and 4095 extremes. 

 
 
 
 
 

Содержание Triac TMC-4

Страница 1: ...mits expansion on the capabilities of the controller to support various communication busses or other control and interface options The TMC4 provides two main positioning options proportional or two p...

Страница 2: ...enu 12 3 4 POSITION CONFIG submenu 13 3 5 COMMS CONFIG submenu 14 3 6 AUX I O CONFIG submenu 15 3 7 SYSTEM CONFIG submenu 16 4 Setup and Calibration 17 4 1 Positioning Devices 17 4 1 1 Feedback Potent...

Страница 3: ...for the TMC4 7 Feedback Potentiometer Header P7 3 point connection header for feedback potentiometer when required for actuator control This provides positioning feedback for when operating as a prop...

Страница 4: ...ementing a setting value the value step increases in value every 6 presses for more rapid adjustment Reset the step back to 1 by pressing back in opposite direction 12 Display OLED screen to show actu...

Страница 5: ...the external brake output energizes The brake setting is currently configured exclusively for use on Triac SRX series actuators and is not configurable Care must be taken when using with other type of...

Страница 6: ...Motor CW AC version Energize clockwise motor winding DC version Switch supply voltage for clockwise operation 6 Motor CCW AC version Energize counterclockwise motor winding DC version Switch supply v...

Страница 7: ...or Electric Actuators Installation Maintenance Manual 7 04 06 22 www atcontrols com IOM08139 REVISION 04 2 2 Wiring Diagrams AC Proportional Control AC Two Position Control DC Proportional Control DC...

Страница 8: ...REVISION 04 2 3 Input Output Signal Configurations Command Type mA Sinking Externally Powered Loop Control Command Type mA Sinking 2 Wire Transmitter Control Command Type 5V and 10V Command Type Poten...

Страница 9: ...TMC 4 Control Card for Electric Actuators Installation Maintenance Manual 9 04 06 22 www atcontrols com IOM08139 REVISION 04 3 Menu...

Страница 10: ...x x x Control CMD Command signal type set in Command Type setting in COMMAND CONFIG submenu FB Feedback signal type set in Feedback Type setting in FEEDBACK CONFIG submenu T E M P E R A T M T R x x x...

Страница 11: ...for the selected command type range Typical values can be found in Section 4 2 1 C A L I B R A T E S P A N x x x x Calibrate Command Span Sets command signal span digital count value When selected pro...

Страница 12: ...mA mA 0 0 to 21 5 mA Disabled When command type is set for ON OFF C A L I B R A T E Z E R O x x x x Calibrate Feedback Zero Sets feedback signal zero digital count value When selected use PREVIOUS or...

Страница 13: ...between 12 bit count of 0 and 4095 based on the measured feedback potentiometer position There is no correct value to set to but it is recommended to fall within the range of 400 3700 C A L I B R A T...

Страница 14: ...COMMAND CONFIG submenu Modbus RTU Modbus RTU Modbus TCP Modbus TCP Profibus Profibus DP U N I T I D x x Unit ID Actuator ID address Selectable from 1 to 246 DEFAULT 1 B A U D R A T E x x x x Baud Rat...

Страница 15: ...When DI2 terminals are powered the TMC4 commands a 100 0 signal and moves to programmed 0 0 position while DI3 detects local input If operating as on off actuator it will drive to the open position li...

Страница 16: ...ount as well as setting for selecting type of motor being operated and restoring factory defaults M O T O R T Y P E x x Motor Type Displays type of motor braking based on if AC version of TMC4 or DC v...

Страница 17: ...ll be 2048 as this is the midpoint value between the limits of 0 and 4095 It is not critical to adjust the potentiometer to exactly 2048 at the 50 position but should be close so that the value will n...

Страница 18: ...ch action 4 1 3 Stop Torque Limit Switch P9 Motor travel stop or torque switches connected to header P9 are used to stop the actuator regardless of set position limits This switch input should be used...

Страница 19: ...rm e Enter Calibrate Span setting and adjust feedback signal using PREVIOUS or NEXT until desired 100 feedback is achieved and confirm Typical feedback signal values are given in 4 2 1 Command and Fee...

Страница 20: ...Y P E L i m i t S W 4 4 Communication Bus Control Calibration For when using one of the optional communication bus add on modules To change values or settings press CONFIRM so value or setting flashe...

Страница 21: ...rmistor provides a temperature dependent resistance that the TMC4 inputs into an algorithm to establish a defined duty cycle limit depending on the measured temperature As the temperature increases th...

Страница 22: ...nge feedback type Incorrect feedback calibration Recalibrate feedback zero and span External loop power being provided Remove external loop power Actuator is hunting Noisy input signal Check input sig...

Страница 23: ...ion 12 bit 4096 points Feedback Signal Out Voltage 0 to 10 8 VDC min 500 load Current 0 to 21 5 mA max 980 load Resolution 12 bit 4096 points Position Feedback Voltage 0 to 3 3 VDC Potentiometer 1k Li...

Страница 24: ...tenance of A T Controls products The user should read and understand the installation operation maintenance IOM instructions included with the product and train its employees and contractors in the sa...

Отзывы: