background image

17

charge line.

• 

Must terminate a maximum of six inches above a floor 

drain or external to the building. In cold climates, it is 

recommended that the discharge pipe be terminated at 

an adequate drain inside the building.

• 

Must be capable of withstanding 250°F (121°C) without 

distortion.

• 

Must be installed to allow complete drainage of both 

the valve and discharge line.

T&P Relief Valve and Pipe Insulation (Some Models) 

1.   Locate the temperature and pressure relief valve on 

the water heater (also known as a T&P relief valve).  

See Figure 15B.

2.   Locate the slit running the length of the T&P relief 

valve insulation.

3.   Spread the slit open and fit the insulation over the T&P 

relief valve.  See Figure 15B.  Apply gentle pressure 

to the insulation to ensure that it is fully seated on the 

T&P Relief Valve. Once seated, secure the insulation 

with duct tape, electrical tape, or equivalent.  

IMPORTANT:

 The insulation or tape should not block 

or cover the T&P relief valve drain opening. Also, the 

insulation or tape should not block or hinder access 

to the manual relief lever (Figure 15B).  Ensure 

that a discharge pipe is installed into the T&P valve 

discharge opening per the instructions in this manual.

4.   Locate the hot water (outlet) & cold water (inlet) pipes 

to the water heater.

5.   Locate the slit running the length of a section of pipe 

insulation.

6.   Spread the slit open and slip the insulation over the cold 

water (inlet) pipe. Apply gentle pressure along the length 

of the insulation to ensure that it is fully seated around 

the pipe. Also, ensure that the base of the insulation is 

flush with the water heater.  Once seated, secure the 

insulation with duct tape, electrical tape, or equivalent.  

7.   Repeat steps 5 and 6 for the hot water (outlet) pipe.

8.   Add additional sections of pipe insulation as needed.

T&P RELIEF VALVE

DRAIN LINE

T&P RELIEF 

VALVE

MANUAL RELIEF 

LEVER

T&P RELIEF VALVE INSULATION

FIGURE 15B.

Combination Space Heating/Potable

 

Water System                                                               

Some water heater models are equipped with inlet/outlet 

connections for use with space heating applications. If this 

water heater is to be used to supply both space heating 

and domestic potable (drinking) water, the instructions 

listed below must be followed.
• 

Be sure to follow the manual(s) shipped with the air 

handler system.

Temperature  and  Pressure  Relief  Valve                     

Explosion Harzard

• Temperature-pressure relief 

valve must comply with ANSI 
Z21.22-CSA 4.4 and ASME 
code.

•  Properly sized temperature-

pressure relief valve must be 
installed in opening provided.

•  Can result in overheating 

and excessive tank pressure.

•  Can cause serious injury or 

death.

METAL
DRAIN PAN

 DRAIN

DRAIN LINE 3/4” 

ID MINIMUM

DISCHARGE PIPE

DO NOT CAP OR PLUG

TEMPERATURE AND PRESSURE RELIEF (T&P)
VALVE (OPTIONAL TOP T&P RELIEF 
VALVE NOT SHOWN)

6” MAXIMUM

AIR GAP

1” MINIMUM

FIGURE 15A.

For protection against excessive pressures and 

temperatures, a temperature and pressure relief valve must 

be installed in the opening marked “T & P RELIEF VALVE” 

(see Figure 15A). This valve must be design certified by 

a nationally recognized testing laboratory that maintains 

periodic inspection of the production of listed equipment or 

materials as meeting the requirements for Relief Valves for 

Hot Water Supply Systems, ANSI Z21.22. The function of 

the temperature and pressure relief valve is to discharge 

water in large quantities in the event of excessive 

temperature or pressure developing in the water heater. 

The valve’s relief pressure must not exceed the working 
pressure of the water heater as stated on the rating plate.
IMPORTANT: Only a new temperature and pressure relief 

valve should be used with your water heater. Do not use an 

old or existing valve as it may be damaged or not adequate 

for the working pressure of the new water heater. Do not 

place any valve between the relief valve and the tank.

The Temperature & Pressure Relief Valve:

• 

Must not be in contact with any electrical part.

• 

Must be connected to an adequate discharge line.

• 

Must not be rated higher than the working pressure 

shown on the rating plate of the water heater.

The Discharge Line:

 

• 

Must not be smaller than the pipe size of the relief 

valve or have any reducing coupling installed in the 

discharge line.

• 

Must not be capped, blocked, plugged or contain any 

valve between the relief valve and the end of the dis-

Содержание GAS WATER HEATER

Страница 1: ...h any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier ca...

Страница 2: ...Pipe Installation 17 Combination Space Heating Potable Water System 17 18 Solar Installation 18 Important Information About this Water Heater 19 Operating Your Water Heater 20 26 Lighting Instruction...

Страница 3: ...ty equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to...

Страница 4: ...period of non use Read instruction manual before installing using or servicing water heater Fire or Explosion Harzard Hydrogen gas can be produced in a hot water system after a period of non use gener...

Страница 5: ...tat T Drain Valve U Manifold Burner Assembly V Flue W Metal Drain Pan X Piezo Igniter Y Base Ring Filter ALL PIPING MATERIALS TO BE SUPPLIED BY CUSTOMERS TO VENT TERMINATION ON ROOF A B D F G H I W V...

Страница 6: ...future users of this water heater will need it for future reference Service to the FVIR System should only be performed by a qualified technician Examples of a qualified technician include licensed pl...

Страница 7: ...the area of the water heater leave the area immediately and call the fire department from a neighbor s home Do not attempt to clean the spill until all ignition sources have been extinguished Fire or...

Страница 8: ...ice used in conjunction with a piped drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to leakage in various ways Sensors mounted in the dr...

Страница 9: ...an L P gas supply Do not connect an L P gas water heater to a natural gas supply Failure to follow these instructions can result in death explosion or carbon monoxide poisoning Explosion Hazard Gas R...

Страница 10: ...in the occurrence of a leak in the system the gas will settle at floor level Basements crawl spaces closets and areas below ground level will serve as pockets for the accumulation of gas Before lighti...

Страница 11: ...y a qualified technician using the installation instructions Examples of a qualified technican include gas technicians authorized gas company personel and authorized service persons Failure to so do c...

Страница 12: ...typical examples of each method Louvers and Grilles In calculating free area for ventilation and combustion air supply openings consideration must be given to the blocking effect of protection louver...

Страница 13: ...y CSA International this certification applies to the vent damper device only and does not mean they are certified for use on this water heater U L recognized fuel gas and carbon monoxide CO detectors...

Страница 14: ...y is clear and free of obstructions The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces Also consult local and state codes for proper chimney sizing and appl...

Страница 15: ...losed System Thermal Expansion 5 Install a shut off valve in the cold water inlet line It should be located close to the water heater and be easily accessible Know the location of this valve and how t...

Страница 16: ...y cause excessive restriction to water flow is not recommended Use only 95 5 tin antimony or other equivalent solder Any lead based solder must not be used Piping that has been treated with chromates...

Страница 17: ...tions If this water heater is to be used to supply both space heating and domestic potable drinking water the instructions listed below must be followed Be sure to follow the manual s shipped with the...

Страница 18: ...water heating appliances when used to supply potable water Some jurisdictions may require a backflow preventer in the incoming cold water line This may cause the temperature and pressure relief valve...

Страница 19: ...t contain negative pressure producing devices such as exhaust fans fireplaces etc Is there a furnace air handler in the same room space as the water heater If so has a return air duct system been atta...

Страница 20: ...e outer door If the Pilot Does Not Light 1 Wait 10 minutes before another lighting attempt If the pilot does not light the Igniter may not be sparking or the unit may not be getting gas or for a new i...

Страница 21: ...hnician or your gas supplier DANGER Hotter water increases the risk of scald injury Consult the instruction manual before changing temperature Refer to the Lighting Instructions in the Installation Ma...

Страница 22: ...49 C 60 C is recommended by most dishwasher manufacturers The thermostat is adjusted to the pilot position when it is shipped from the factory Water temperature can be regulated by moving the temperat...

Страница 23: ...the heated water may vary Operating Modes and Settings Standard Mode The controller adjusts the water heater to maintain the temperature set by the user Vacation Setting The Vacation setting VAC sets...

Страница 24: ...ater conditioning company to successfully eliminate all water odor problems Artificially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium i...

Страница 25: ...water heater drain valve and allow all of the water to drain from the tank Flush the tank with water as needed to remove sediment 6 Close the drain valve refill the tank and restart the water heater...

Страница 26: ...d billed accordingly When ordering replacement parts always have the following information ready 1 model serial and product number 2 type of gas 3 item number 4 parts description See Repair Parts Sect...

Страница 27: ...ILOT THERMOPILE ASSEMBLY PILOT THERMOPILE ASSEMBLY IGNITER CONNECTOR THERMAL SWITCH CONNECTORS PILOT THERMOPILE THERMOPILE CONNECTOR WHITE WIRE RED WIRE PILOT TUBE NOT SHOWN FOR CLARITY FIGURE 26 7 Ro...

Страница 28: ...ort if glass is missing or damaged removed Replace door gasket if damaged Failure to follow these instructions can result in death explosion or fire 1 Check the door gasket for damage or imbedded debr...

Страница 29: ...Figure 19A 2 Turn off the gas at the manual shut off valve on the gas supply pipe Figure 3 3 Drain the water heater Refer to the section of Draining and Flushing and follow the procedure 4 Disconnect...

Страница 30: ...ostat temperature limit was ex ceeded Status light will blink 4 flashes 11 Pilot line or orifice clogged 12 Non functioning thermopile 13 Air for combustion obstructed 14 FVIR Flame Arrestor blocked w...

Страница 31: ...section 5 Clean filter See Cleaning the Combustion Chamber and Flame Arrestor section SMOKING AND CARBON FORMATION SOOTING 1 Insufficient combustion air 2 Low gas pressure 3 Water heater flue or vent...

Страница 32: ...on if the return air duct is in the same location Correct size of openings to allow sufficient air NO YES YES NO Section C Pilot light will not remain lit Complete this section after completing Sectio...

Страница 33: ...water heater has been operating but has stopped and will not re light check the flame arrestor for signs of high temperature blue or black discoloration indicating a flammable vapor incident If you s...

Страница 34: ...mostat 8 FLASHES This condition only appears if the gas control temperature knob has been turned off and the thermopile continued to produce electric power This condition can occur if the thermopile d...

Страница 35: ...35 NOTES...

Страница 36: ...1 DRAFT HOOD 2 HEAT TRAP COLD SOME MODELS 3 HEAT TRAP HOT SOME MODELS 4 COLD WATER DIP TUBE 5 ANODE ROD 6 TEMPERATURE PRESSURE RELIEF VALVE LOCATED TOP OR SIDE 7 DRAIN VALVE 8 GAS CONTROL VALVE THERM...

Страница 37: ...12B Burner L P Gas Item 13A Manifold Burner Assembly contains the door gasket manifold tube pilot thermopile assembly manifold component block thermal switch and burner Natural Gas Low Nox Item 13B M...

Страница 38: ...on location in the United States its territories or possessions and Canada sized in accordance with proper sizing techniques for residential water heaters bearing a rating plate which has not been alt...

Страница 39: ...M DOES NOT CONSTITUTE PROOF OF PURCHASE OR PROOF OF INSTALLATION DISCLAIMERS NO EXPRESSED WARRANTY HAS BEEN OR WILL BE MADE ON BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER...

Страница 40: ...40 Copyright 2010 A O Smith Corporation All rights reserved...

Отзывы: