14

Align the legs of the draft hood with the slots provided. 

Insert the legs and secure the draft hood to the water 

heater’s top with the four screws provided as shown in 

Figure 9. Do not alter the draft hood in any way. If you are 

replacing an existing water heater, be sure to use the draft 

hood supplied with this water heater.

Vent Pipe Size                                                               

It is important that you follow the guidelines in these 

instructions for sizing a vent pipe system. If a transition 

to a larger vent size is required, the vent transition 

connection must be made at the draft hood outlet.

Vent Connectors                                                          

1.  Type B, Double wall, U.L. Listed Vent Pipe.
2.  Single wall Vent Pipe.
Maintain the manufacturer’s specified minimum clearance 

from combustible materials when using type B double wall 

vent pipe.
Vent connectors made of type B, double wall vent pipe 

material may pass through walls or partitions constructed 

of combustible material if the minimum listed clearance is 

maintained.
Maintain a six inch minimum clearance from all 

combustible materials when using single wall vent pipe.
IMPORTANT: Single wall vent pipe cannot be used for 

water heaters located in attics and may not pass through 

attic spaces, crawl spaces or any confined or inaccessible 

location. A single wall metal vent connector cannot pass 

through any interior wall.
When installing a vent connector, please note the following 

(See Figures 10-12):
• 

Install the vent connector avoiding unnecessary bends, 

which create resistance to the flow of vent gases.

• 

Install without dips or sags with an upward slope of at 

least 1/4-inch per foot.

• 

Joints must be fastened by sheet metal screws or other 

approved means. It must be supported to maintain 

clearances and prevent separation of joints and 

damage.

• 

The length of the vent connector cannot exceed 75% of 

the vertical vent height.

• 

The vent connector must be accessible for cleaning, 

inspection, and replacement.

• 

Vent connectors cannot pass through any ceiling, floor, 

firewall, or fire partition.

• 

It is recommended (but not mandatory) that a minimum 

12 inches of vertical vent pipe be installed on the draft 

hood prior to any elbow in the vent system.

IMPORTANT: Existing vent systems must be inspected for 

obstructions, corrosion, and proper installation.

Chimney Connection                                                  

IMPORTANT: Before connecting a vent to a chimney, 

make sure the chimney passageway is clear and free of 

obstructions. The chimney must be cleaned if previously 

used for venting solid fuel appliances or fireplaces. Also 

consult local and state codes for proper chimney sizing 

and application or, in the absence of local and state 

codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 

54)-current edition.

• 

The connector must be installed above the extreme 

bottom of the chimney to prevent potentially blocking 

the flue gases.

• 

The connector must be firmly attached and sealed to 

prevent it from falling out.

• 

To aid in removing the connector, a thimble or slip joint 

may be used.

• 

The connector must not extend beyond the inner edge 

of the chimney as it may restrict the space between it 

and the opposite wall of the chimney (Figure 10).

LISTED LINED
CHIMNEY

2 FT. MINIMUM ABOVE ANY OBJECT 
WITHIN 10FT. HORIZONTALLY

DO NOT EXTEND 
VENT BEYOND EDGE
OF CHIMNEY

VENT
CONNECTOR

 

3 FT. MINIMUM

 

MAINTAIN
CLEARANCE*

SEAL 

SLOPE

UP 1/4 IN.

PER FT.

MINIMUM

CHIMNEY TERMINATION VENT SYSTEM

SUPPORT
STRAP

FIGURE 10.

Do not terminate the vent connector in a chimney that has 

not been certified for this purpose. Some local codes may 

prohibit the termination of vent connectors in a masonry 

chimney.

Vertical Exhaust Gas Vent                                          

Vertical exhaust gas vents must be installed with 

U.L. listed type B vent pipe according to the vent 

manufacturer’s instructions and the terms of its listing. 
It must be connected to the water heater’s draft hood by a 

listed vent connector or by directly originating at the draft 

hood opening.
Vertical gas vents must terminate with a listed cap or 

other roof assembly and be installed according to their 

manufacturer’s instructions.
Gas vents must be supported to prevent damage, joint 

separation, and maintain clearances to combustible 

materials (Figures 11 and 12).
IMPORTANT: This gas vent must be terminated in a 

vertical position to facilitate the removal of the burnt gases.
An unused chimney flue or masonry enclosure may be used 

as a passageway for the installation of a gas vent (Figure 12).
Common (combined) venting is allowable with vertical type 

B vent systems and lined masonry chimneys as long as 

proper draft for the water heater is established under all 

conditions of operation. CAUTION: DO NOT common vent 

this water heater with any power vented appliance.
Figures 10-12 are examples of vent pipe system 

installations and may or may not be typical for your 

specific application. Consult the “National Fuel Gas Code”, 

NFPA 54, ANSI Z223.1-current edition and the guidelines 

set forth by prevailing local codes.

Содержание GAS WATER HEATER

Страница 1: ...h any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier ca...

Страница 2: ...Pipe Installation 17 Combination Space Heating Potable Water System 17 18 Solar Installation 18 Important Information About this Water Heater 19 Operating Your Water Heater 20 26 Lighting Instruction...

Страница 3: ...ty equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to...

Страница 4: ...period of non use Read instruction manual before installing using or servicing water heater Fire or Explosion Harzard Hydrogen gas can be produced in a hot water system after a period of non use gener...

Страница 5: ...tat T Drain Valve U Manifold Burner Assembly V Flue W Metal Drain Pan X Piezo Igniter Y Base Ring Filter ALL PIPING MATERIALS TO BE SUPPLIED BY CUSTOMERS TO VENT TERMINATION ON ROOF A B D F G H I W V...

Страница 6: ...future users of this water heater will need it for future reference Service to the FVIR System should only be performed by a qualified technician Examples of a qualified technician include licensed pl...

Страница 7: ...the area of the water heater leave the area immediately and call the fire department from a neighbor s home Do not attempt to clean the spill until all ignition sources have been extinguished Fire or...

Страница 8: ...ice used in conjunction with a piped drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to leakage in various ways Sensors mounted in the dr...

Страница 9: ...an L P gas supply Do not connect an L P gas water heater to a natural gas supply Failure to follow these instructions can result in death explosion or carbon monoxide poisoning Explosion Hazard Gas R...

Страница 10: ...in the occurrence of a leak in the system the gas will settle at floor level Basements crawl spaces closets and areas below ground level will serve as pockets for the accumulation of gas Before lighti...

Страница 11: ...y a qualified technician using the installation instructions Examples of a qualified technican include gas technicians authorized gas company personel and authorized service persons Failure to so do c...

Страница 12: ...typical examples of each method Louvers and Grilles In calculating free area for ventilation and combustion air supply openings consideration must be given to the blocking effect of protection louver...

Страница 13: ...y CSA International this certification applies to the vent damper device only and does not mean they are certified for use on this water heater U L recognized fuel gas and carbon monoxide CO detectors...

Страница 14: ...y is clear and free of obstructions The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces Also consult local and state codes for proper chimney sizing and appl...

Страница 15: ...losed System Thermal Expansion 5 Install a shut off valve in the cold water inlet line It should be located close to the water heater and be easily accessible Know the location of this valve and how t...

Страница 16: ...y cause excessive restriction to water flow is not recommended Use only 95 5 tin antimony or other equivalent solder Any lead based solder must not be used Piping that has been treated with chromates...

Страница 17: ...tions If this water heater is to be used to supply both space heating and domestic potable drinking water the instructions listed below must be followed Be sure to follow the manual s shipped with the...

Страница 18: ...water heating appliances when used to supply potable water Some jurisdictions may require a backflow preventer in the incoming cold water line This may cause the temperature and pressure relief valve...

Страница 19: ...t contain negative pressure producing devices such as exhaust fans fireplaces etc Is there a furnace air handler in the same room space as the water heater If so has a return air duct system been atta...

Страница 20: ...e outer door If the Pilot Does Not Light 1 Wait 10 minutes before another lighting attempt If the pilot does not light the Igniter may not be sparking or the unit may not be getting gas or for a new i...

Страница 21: ...hnician or your gas supplier DANGER Hotter water increases the risk of scald injury Consult the instruction manual before changing temperature Refer to the Lighting Instructions in the Installation Ma...

Страница 22: ...49 C 60 C is recommended by most dishwasher manufacturers The thermostat is adjusted to the pilot position when it is shipped from the factory Water temperature can be regulated by moving the temperat...

Страница 23: ...the heated water may vary Operating Modes and Settings Standard Mode The controller adjusts the water heater to maintain the temperature set by the user Vacation Setting The Vacation setting VAC sets...

Страница 24: ...ater conditioning company to successfully eliminate all water odor problems Artificially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium i...

Страница 25: ...water heater drain valve and allow all of the water to drain from the tank Flush the tank with water as needed to remove sediment 6 Close the drain valve refill the tank and restart the water heater...

Страница 26: ...d billed accordingly When ordering replacement parts always have the following information ready 1 model serial and product number 2 type of gas 3 item number 4 parts description See Repair Parts Sect...

Страница 27: ...ILOT THERMOPILE ASSEMBLY PILOT THERMOPILE ASSEMBLY IGNITER CONNECTOR THERMAL SWITCH CONNECTORS PILOT THERMOPILE THERMOPILE CONNECTOR WHITE WIRE RED WIRE PILOT TUBE NOT SHOWN FOR CLARITY FIGURE 26 7 Ro...

Страница 28: ...ort if glass is missing or damaged removed Replace door gasket if damaged Failure to follow these instructions can result in death explosion or fire 1 Check the door gasket for damage or imbedded debr...

Страница 29: ...Figure 19A 2 Turn off the gas at the manual shut off valve on the gas supply pipe Figure 3 3 Drain the water heater Refer to the section of Draining and Flushing and follow the procedure 4 Disconnect...

Страница 30: ...ostat temperature limit was ex ceeded Status light will blink 4 flashes 11 Pilot line or orifice clogged 12 Non functioning thermopile 13 Air for combustion obstructed 14 FVIR Flame Arrestor blocked w...

Страница 31: ...section 5 Clean filter See Cleaning the Combustion Chamber and Flame Arrestor section SMOKING AND CARBON FORMATION SOOTING 1 Insufficient combustion air 2 Low gas pressure 3 Water heater flue or vent...

Страница 32: ...on if the return air duct is in the same location Correct size of openings to allow sufficient air NO YES YES NO Section C Pilot light will not remain lit Complete this section after completing Sectio...

Страница 33: ...water heater has been operating but has stopped and will not re light check the flame arrestor for signs of high temperature blue or black discoloration indicating a flammable vapor incident If you s...

Страница 34: ...mostat 8 FLASHES This condition only appears if the gas control temperature knob has been turned off and the thermopile continued to produce electric power This condition can occur if the thermopile d...

Страница 35: ...35 NOTES...

Страница 36: ...1 DRAFT HOOD 2 HEAT TRAP COLD SOME MODELS 3 HEAT TRAP HOT SOME MODELS 4 COLD WATER DIP TUBE 5 ANODE ROD 6 TEMPERATURE PRESSURE RELIEF VALVE LOCATED TOP OR SIDE 7 DRAIN VALVE 8 GAS CONTROL VALVE THERM...

Страница 37: ...12B Burner L P Gas Item 13A Manifold Burner Assembly contains the door gasket manifold tube pilot thermopile assembly manifold component block thermal switch and burner Natural Gas Low Nox Item 13B M...

Страница 38: ...on location in the United States its territories or possessions and Canada sized in accordance with proper sizing techniques for residential water heaters bearing a rating plate which has not been alt...

Страница 39: ...M DOES NOT CONSTITUTE PROOF OF PURCHASE OR PROOF OF INSTALLATION DISCLAIMERS NO EXPRESSED WARRANTY HAS BEEN OR WILL BE MADE ON BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER...

Страница 40: ...40 Copyright 2010 A O Smith Corporation All rights reserved...

Отзывы: