Installation Manual
H3C S7500 Series Ethernet Switches
Appendix B N68 Cabinet Installation
B-77
Note:
z
In the figure: (1) indicates a dummy panel; (2) indicates a cabling frame; (3)
indicates a nonstandard mini panel
z
Small squares in the figure indicate guide rails.
z
A1 through H1 and A2 through H2 are guide rails at the corresponding positions.
z
M1 through M13 indicate dummy panels at the corresponding positions in the
standard configuration.
z
In a DC cabinet, you may need to remove the M13 in the upper most, and move the
DC power distribution component which originally locates at the rear of the cabinet
to this position.
z
In AC cabinets, M13 does not exist, and the position is for the AC power distribution
component.
z
The S7500 series and other devices that comply with the N68 cabinet size can be
installed in the cabinet.
z
You need not to use the cabinet exactly as the figure shows, but can adjust the
position of guild rails and dummy panels as needed.
z
The dummy panels are for comeliness purpose only, so that you need not to install
them when they are in shortage.
z
The power of your device should be within the range allowed by the air breaker.
Refer to power distribution part for details.
z
The squares with shadow marks in the figure represent the four-hole guide rails,
which can bear a weight of 90 KG; and the squares without shadow marks represent
the two-hole guide rails, which can bear a weight of 40 KG.
Table B-17
Symbol description
Symbol
Description
S
Indicates standard configuration (configured with one S7503 chassis)
A
Configured with two S7503 chassis
B
Configured with one S7506 chassis
C
Configured with two S7506 chassis
D
Configured with one S7506R chassis
E
Configured with two S7506R chassis
The methods of remodeling standard configuration to other configuration are as
follows:
1)
Remodeling standard configuration to configuration A: Remove dummy panel M7
and M8. The result of the remodeling is configuration A.