Installation Manual
H3C S7500 Series Ethernet Switches
Appendix A B68-22 Cabinet Installation
A-34
(1) Anchor strip retaining nut
(2) Anchor strip
(3) M16 cabinet foot
(4) Insulating washer of the strip
(5) M12 × 70 bolt
(6) Spring washer 12
(7) Big flat washer 12
(8) Insulation washer
Figure A-37
Install anchor strips
IV. Fixing the retaining nuts of the anchor strips
Fasten the retaining nut on the anchor strip as shown in area B in Figure A-37 and
torque the bolts to 45 Nm.
A.3.11 Testing Insulation
Switch the multimeter to Mohm range and measure the resistance between the
fastening bolts M12 × 70 and the anchor strips. If the resistance is larger than five
Mohm, you can finish installation. If not, remove all anchor strip parts, check that the
insulation washers are installed and without damage, reinstall, and measure insulation