Installation Manual
H3C S7500 Series Ethernet Switches
Appendix B N68 Cabinet Installation
B-21
Figure B-20
A row of cabinets installed on cement floor
V. Verifying installation
The following requirements must be satisfied:
z
Cabinet arrangement, installation positions, and directions must satisfy the
requirements of the construction design.
z
The front, back, left, and right surfaces of the cabinets should be perpendicular to
the floor. The horizontal and vertical tolerance must be less than or equal to 3 mm
(0.1 in.).
z
The cabinets must be in a straight line near the primary walkway. The tolerance
must be less than or equal to 5 mm (0.2 in.). Adjacent cabinets must be closed up.
A whole row of cabinets must be flush.