Installer Programming

Control Panel Programming Questions

Q-5 

Enter  exit delay, in seconds (45-120)

DEFAULT: 60 seconds

 (Required SIA CP-01 Default)

The Exit Delay can be set from 45 to 120 seconds.

•  The default (60) sets the Exit Delay to 60 seconds.
•  To change the Exit Delay, enter a value from (45-120) seconds.

 

NOTE: This default can be changed without affecting SIA CP-01 compliance.

Q-6 

Enter  entry delay 1, in seconds (30-240)

DEFAULT: 30 seconds

 (Required SIA CP-01 Default)

The Entry Delay #1 can be set from 30 to 240 seconds.

•  The default (30) sets the Entry Delay #1 to 30 seconds.
•  To change the Entry Delay #1, enter a value from (30-240) seconds.

 

NOTE: Per SIA CP-01, the combination of the Abort Window Dialer Delay 
(Q-35) and the Entry Delay (Q-6 or Q-7) cannot exceed one minute.

Q-7 

Enter  entry delay 2, in seconds (30-240)

DEFAULT: 45 seconds

 (Required SIA CP-01 Default)

The Entry Delay #2 can be set from 30 to 240 seconds.

•  The default (45) sets the Entry Delay #2 to 45 seconds.
•  To change the Entry Delay #2, enter a value from (30-240) seconds.

 

NOTE: Per SIA CP-01, the combination of the Abort Window Dialer Delay 
(Q-35) and the Entry Delay (Q-6 or Q-7) cannot exceed one minute.

Q-8 

Select  dialer (0-1)

DEFAULT: Disabled (0)

The dialer (digital communicator) can be enabled for a monitored system or 
disabled for a local alarm or when the GSM module is used exclusively for 
reporting.

•  The default (0) sets the dialer as disabled.
•  To turn on the dialer, select enabled (1).

 

NOTE: If the dialer is disabled with this programming question, 
telephone line failure detection is also disabled regardless of 
the setting of the telephone fail detection question Q-63.

Q-9 

Enter  dialing prefi x (0-4 digits)

DEFAULT: No default

Some telephone PBX systems require a dialing prefi x to acquire a dial tone.

•  If the telephone system that the Control Panel is connected 

to requires a dialing prefi x, enter up to four digits.

• The 

SHIFT

 button accesses the pound and star symbols. 

The 

P

 button adds a 3-second pause to the dialing.

Q-10 

Enter  call waiting disable code (0-6 digits)

DEFAULT: No default

 (Required SIA CP-01 Default)

If the subscriber’s telephone line has call waiting, incoming call tones on the line 
could interfere with a communicator report to the Central Station. To prevent this, 
the communicator can send the call waiting disable code before making a report.

•  If call waiting is active on the telephone line, 

enter the call waiting disable code.

• The 

SHIFT

 button accesses the pound and star symbols. 

The 

P

 button adds a 3-second pause to the dialing.

 

NOTE: If the fi rst attempt fails, this code will be 
ignored on the rest of the attempts.

Q-11 

Enter  CS #1 phone number (0-25 digits)

DEFAULT: No default

The telephone number for Central Station #1 can be up to 25 digits.

•  Enter the Central Station #1 telephone number.
• The 

SHIFT

 button accesses the pound and star symbols. 

The 

P

 button adds a 3-second pause to the dialing.

 

NOTE: If a second Central Station telephone number is programmed 
with question Q-41, the Control Panel will alternate between the 
two Central Station telephone numbers. After two failed telephone 
dialing attempts, the Control Panel will try to connect using the 
GSM radio module if it is installed. If the GSM radio module is not 
installed, the Control Panel will make eight dialing attempts.

Q-12 

Enter  CS #1 account number (4 digits)

DEFAULT: No default

The account number for Central Station #1 is always four digits and can include 
some alpha characters.

•  Enter four digits for the Central Station #1 account number.
• The 

SHIFT

 button accesses B, C, D, E, and F characters.

Q-13 

Select  2-way voice (0-2)

DEFAULT: Stay on line (1)

The Control Panel supports 2-way voice communications between the subscriber 
and the Central Station operator over the telephone line or the GSM cellular radio 
(if installed) after an alarm has been reported.

•  The default (1) allows 2-way audio over the telephone line or GSM radio.
•  Selecting (2) allows 2-way audio over the telephone 

line or GSM radio during fi re and CO alarms.

•  To turn off the 2-way audio feature, select disabled (0).

When the Control Panel connects with the operator, it will beep once per second 
(every six seconds with a GSM connection).  The beep alternates between two tones 
and indicates the panel is waiting for a session command. If the operator fails to issue 
a command within one minute (three minutes with a GSM connection), the call is 
terminated. Once the operator presses a command option, the beeps will stop and 
a 5-minute audio session will start (3-minute audio session with a GSM connection).

 When 2-way voice communications have been established, the Central Station 
operator can use the following telephone keys to control the communications. 
Each time the operator uses a command key, the session is extended for fi ve 
additional minutes (three minutes with a GSM connection). During the last minute 
of communications, the system will  beep twice every 15 seconds to indicate that 
time is running out.

• Pressing   enables Talk Mode one-way communication from 

the CS to the Premises and allows the operator to talk.

• Pressing   enables VOX Mode two-way 

communications from the CS to the premises.

• Pressing   enables Listen Mode one-way 

communication from the premises to the CS.

• Pressing   extends the session fi ve minutes 

without changing the mode of operation.

• Pressing   causes the audio session to end and terminates the call.

Q-14 

Select silent panic/burglary  listen only

DEFAULT: Enabled (1)

The Control Panel supports audio listen-in of the subscriber premises from the 
Central Station over the telephone line after a silent panic (police emergency), 
silent burglary, or duress alarm has been reported.

•  The default (1) enables audio listen-in after a silent 

panic, silent burglary, or duress alarm.

•  This option is permanently set and cannot be disabled.

Содержание GO!control 2GIG-CNTRL2

Страница 1: ...Wireless Security System Installation Programming Instructions 2GIG CNTRL2 2GIG CP2...

Страница 2: ...e ceiling Do not install smoke alarms where normal ambient temperatures are above 100 F 37 8 C or below 40 F 4 C Also do not locate alarm in front of air conditioners heating registers or other locati...

Страница 3: ...ounder Disable Icon 14 Backup Battery Status Icon 14 Test Mode Icon 14 Touch Screen Keypad Traffic Icon 14 GSM Radio Icon 14 Interior Sensor Open Icon 14 Programming Navigation 15 Navigation Arrows Go...

Страница 4: ...requirements to qualify for a discount For an ETL smoke alarm system use only approved model smoke detectors with this Control Panel NOTE Some cities and municipalities may require an alarm system per...

Страница 5: ...subscribers can query and control their system using a computer browser from anywhere in the world The Alarm com server can also send messages time corrections and software updates to the Control Pan...

Страница 6: ...lashes ORANGE when ANY sensor is open not ready to arm Flashes RED while system is armed HOME BUTTON INDICATOR THIRD HAND HANGER STRAP Hooks onto mounting plate during installation to hold the Control...

Страница 7: ...ery connector into the connector on the Control Panel s circuit board 14 Swing the Control Panel up placing the bottom over the lip of the mounting bracket Push the top of the Control Panel into the m...

Страница 8: ...second button lockout Lithium battery 345 MHz ETL Listed 2GIG GB1 Glass Break Detector Monitors for the sound of breaking glass Two test LEDs Dual shatter recognition technology thud then crash Lithiu...

Страница 9: ...module Locking connector 2GIG ANT4X External In wall GSM Antenna Antenna installs in the wall behind Control Panel 2 foot cable Plugs into GSM module Locking connector 2GIG BATT1 Standard Battery Pac...

Страница 10: ...rmally open N O or normally closed N C End of line resistors EOLR can also be used to supervise the loops Only contacts should be used with the hardwired loops The Control Panel does not support power...

Страница 11: ...LCO INPUT DROP SIDE OFTHE BOX OR ANY EARTH GROUNDS 3 At the demarcation box connect the RED cable wire to the box RING and the GREEN cable wire to the box TIP 4 At the demarcation box connect the BLAC...

Страница 12: ...as simply plug the antenna connector into the GSM module The antenna will drop into the wall or mount in the attic with the cable passing through the slot in the Control Panel s mounting plate See Fig...

Страница 13: ...ug the backup battery pack s connector into the connector on the Control Panel s circuit board The Control Panel will not recognize that the battery is connected until AC power is connected to the pow...

Страница 14: ...e displayed To arm the system without an entry delay un check the ENTRY DELAY check box To arm silently without sounding the Exit Delay beeps check the SILENT EXIT check box Stay Mode arming always ha...

Страница 15: ...shortcut to help the installer access the Installer Toolbox quickly Pressing the lower right corner of the Home Screen while the system is disarmed will immediately display a code entry screen When t...

Страница 16: ...he system is being tested in Walk Test Mode the test mode icon will be displayed on the status bar Touch Screen KeypadTraffic Icon When the Control Panel is communicating to a touch screen keypad the...

Страница 17: ...utton advances to the next programming question section The arrows select the next or previous programming sub question The arrows choose values for the question or move the cursor left and right alon...

Страница 18: ...allation The volume setting DOES NOT affect the volume of alarm sounds 9 Press to view the second toolbox screen 10 Press BACKLIGHTTIMEOUT and set the display lighting timeout 11 Press SET DATE and SE...

Страница 19: ...delay restart 0 1 1 enabled Q QUESTION DEFAULT Q 28 Select quick exit 0 1 1 enabled Q 29 Enter periodic test in days 0 255 30 days Q 31 Enter cancel time in minutes 5 255 5 minutes Q 32 Select cancel...

Страница 20: ...ion trouble report but not an alarm when the system is disarmed 06 24 hour Silent Alarm This sensor type is active independent of the system arming status The code for silent panic is sent to the Cent...

Страница 21: ...LAUNDRY 127 LEFT 128 LEVEL 129 LIBRARY 130 LIGHT 131 LIGHTS 132 LIQUOR 133 LIVING 134 LOADING 135 LOCK 136 LOFT 137 LOW WORD 138 MAIN 139 MAINTENANCE 140 MASTER 141 MEDICAL 142 MEDICINE 143 MENU 144 M...

Страница 22: ...umber 01 48 Sensor Type Exit entry perimeter interior etc Sensor Equipment Type Certain sensor types will ask for equipment type Sensor Equipment Code Sensor model door window PIR smoke detector etc S...

Страница 23: ...ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR insert PRESS...

Страница 24: ...arrows or enter the equipment type number directly on the keypad Select RF sensor equipment code DEFAULT 0000 other The equipment code is a 4 digit code that is assigned to the model of sensor being u...

Страница 25: ...button can be used to recall the last programmed sensor s serial number The sensor number will be filled in automatically if LEARN is used Select RF sensor dialer delay 0 1 DEFAULT Enabled 1 Required...

Страница 26: ...announcement and chime options for the sensor Wired Sensor Summary Screen After setting all the options for a sensor the wired sensor summary screen is displayed The screen can also be displayed for p...

Страница 27: ...ol Panel can be used with new or existing wired sensors If this wired sensor is new for the installation leave the default of new 0 If this wired sensor is already installed select existing 1 Select w...

Страница 28: ...button RF Key Fob Summary Screen After setting all the options for a sensor the key fob summary screen is displayed The screen can also be displayed for programmed key fobs during key fob program edit...

Страница 29: ...quipment age 0 1 DEFAULT New 0 The Control Panel can be used with new or existing key fobs If this fob is new for the installation leave the default of new 0 If this fob is already installed select ex...

Страница 30: ...een After setting all the options for a sensor the RF keypad summary screen is displayed The screen can also be displayed for programmed RF keypads during RF keypad program editing by pressing the SUM...

Страница 31: ...the Control Panel will learn the RF keypad s serial number TS1 WirelessTouch Screen Keypads For 2GIG TS1 Wireless Touch Screen Keypads press LEARN The Control Panel will display Pair with TS 1 Initia...

Страница 32: ...HIFT button accesses the pound and star symbols The P button adds a 3 second pause to the dialing NOTE If a second Central Station telephone number is programmed with question Q 41 the Control Panel w...

Страница 33: ...e supervised If the wiring to the sounder is cut for 15 30 or 45 seconds a bell trouble report can be sent to the Central Station The default 0 disables external sounder supervision To supervise the e...

Страница 34: ...information on setting the cancel report trigger time NOTE This default can be changed without affecting SIA CP 01 compliance Q 33 Select cross sensor 47 48 0 1 DEFAULT Disabled 0 The Control Panel c...

Страница 35: ...sses B C D E and F characters Q 42 Select remote control phone 0 3 DEFAULT Data and voice 3 This setting controls remote telephone access to the system The data option is for the installer It allows a...

Страница 36: ...trouble beeps from sounding from 10 pm to 9 am The trouble s will still be displayed and immediately reported to the Central Station and can be acknowledged but they won t sound beeps until after 9 a...

Страница 37: ...shutdown until the time of disarm and the sensor is closed The default 0 prevents alarm restore reports To allow alarm restore reports select enabled 1 Q 58 Select trouble restore reports to CS 0 1 DE...

Страница 38: ...light saving end week Q 71 Select system tamper causes trouble 0 1 DEFAULT Enabled 1 The Control Panel s case has a tamper switch that detects if the case has been opened The system can be programmed...

Страница 39: ...isible 1 The Z Wave home services feature can be enabled or disabled with various remote control access options The default 1 displays the SERVICES button but will show a message that the feature is c...

Страница 40: ...1 DEFAULT Disabled 0 This setting enhances system operation in personal emergency applications and also provides the dealer with the option of the siren sounding until the bell cut off or to the end...

Страница 41: ...permitted 4 Setup each User Code with the User Access Option Screen Each User Code can be set to be currently valid or not or to have conditional validity depending on a time and date schedule Refer...

Страница 42: ...ome active again To re enable the sounder manually follow these steps 1 From the Installer Toolbox Screen press ENABLE SOUNDER 2 A confirmation screen will be displayed Press OK Zone ReportingTest To...

Страница 43: ...est report to the Central Station Exiting the Walk Test Mode will send a stop test report to the Central Station To perform a walk test follow these steps 1 From the Installer Toolbox screen press WAL...

Страница 44: ...Installer Toolbox TelephoneTest The telephone test checks the land line connection to the Central Station through the Control Panel s built in digital communicator The test is accessed through the Us...

Страница 45: ...s Industry Canada Notices NOTICE The ringer equivalence number REN assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone int...

Страница 46: ...exit delay restart 0 1 1 enabled Q QUESTION DEFAULT Q 28 Select quick exit 0 1 1 enabled Q 29 Enter periodic test in days 0 255 30 days Q 31 Enter cancel time in minutes 5 255 5 minutes Q 32 Select c...

Страница 47: ...126 LAUNDRY 127 LEFT 128 LEVEL 129 LIBRARY 130 LIGHT 131 LIGHTS 132 LIQUOR 133 LIVING 134 LOADING 135 LOCK 136 LOFT 137 LOW WORD 138 MAIN 139 MAINTENANCE 140 MASTER 141 MEDICAL 142 MEDICINE 143 MENU...

Страница 48: ...46 Notes...

Страница 49: ...47 Notes...

Страница 50: ...panel internal features 4 Control panel location 5 Control panel location height 5 Control panel mounting 11 Control panel mounting plate 8 Control panel wiring 11 Control panel wiring diagram 2 Cross...

Страница 51: ...31X telephone jack 9 S Saving programming 39 Security screen 12 Select keyfob remote arming mode on system not ready 38 Select siren mode 38 Sensor signal loss through materials 5 Sensor types 18 Sens...

Страница 52: ...v1 9 233497 E Copyright 2012...

Отзывы: