 System Sensor Types

 Each sensor (wireless or wired) installed in the system is 
programmed to a specifi c sensor number and sensor type (  zone).

The 

sensor number

 identifi es the specifi c sensor when it is 

displayed on the Control Panel, recorded in the event log, or 
reported to the Central Station. This allows pin-point information 
about any sensor in the system.

The 

sensor type

 determines how and when the Control Panel 

responds to signals from the sensor. Some sensors are armed 
all the time, others are armed only in certain arming levels, some 
cause Central Station reports any time they are activated. The 
sensor’s type, along with other programming options, determine 
this.

Sensor Types  (Zones)

 (00)  Unused

This is the setting for unused sensor numbers that do not have a sensor 
programmed into them. No system action occurs at any time from this sensor 
type.

(01)  Exit/Entry 1

This sensor type is reserved for doors that are used for exit and entry of the 
protected premises. When the system is armed in the Away Mode or Stay Mode, 
the Exit Delay timer starts. There is an Exit Delay regardless of whether the 
system is armed in Stay Mode or Away Mode. When the Exit Delay timer expires, 
the system is fully armed.

With the system fully armed, when this type of sensor is triggered, the Entry 
Delay #1 timer starts. The system must be disarmed before the Entry Delay #1 
time expires, or an alarm will occur.

If the Entry Delay is turned off during arming, the exit/entry delay sensors will act 
as non-delayed instant sensors at the end of Exit Delay.

(02)  Exit/Entry 2

This sensor type operates the same as the Exit/Entry 1 sensor type except it will 
start the Entry Delay #2 timer. This provides a method of having a longer Entry 
Delay on certain openings, such as a garage door, to provide the user more time 
to disarm the system.

(03)  Perimeter

This sensor type is for perimeter doors and windows that will not be used to enter 
or exit the protected premises while the system is armed.

An instant alarm will occur when this type of sensor is triggered with the system 
armed in either the Stay Mode or Away Mode.

(04)  Interior Follower

This sensor type is for interior sensors such as motion detectors, mat switches, 
interior doors, and other sensors that detect human presence inside the protected 
premises.

This type of sensor is called a “follower” due to its action when the system is 
armed in the Away Mode. After the Exit Delay expires and the system is armed, if 
an interior follower sensor is triggered, an instant alarm will occur. If an exit/entry 
delay sensor is triggered fi rst, the interior follower sensor will also be delayed.

Interior follower sensors are always bypassed and not active when the system is 
armed in Stay Mode. This allows the premises to be occupied while still protecting 
the perimeter.

(05)  Day Zone

This sensor type is the same as a perimeter zone, except when the system is 
disarmed, a violation displays a trouble alert on the Console’s display.

Common uses for this sensor type are protection of sensitive areas that require 
notifi cation and possibly a Central Station trouble report, but not an alarm when 
the system is disarmed.

(06)  24-hour Silent Alarm

This sensor type is active independent of the system arming status. The code 
for silent panic is sent to the Central Station, but for safety, there are no visual or 
audible indications locally that this sensor type has been triggered.

(07)  24-hour Audible Alarm

This sensor type is continuously armed 24-hours a day. A sensor programmed to 
this type will trigger a local alarm and the bell output regardless of the mode the 
system is in. Typical use would be an audible panic alarm.

(08)  24-hour Auxiliary Alarm

This sensor type is continuously armed 24-hours a day. A sensor programmed 
to this type will trigger an alarm regardless of the mode the system is in. The bell 
output will not activate, but the local sounder will continue until it’s acknowledged 
at the Control Panel. Typical use would be for a monitoring device such as a fl ood 
or temperature sensor. There is no timeout for the internal sounder, it will continue 
until a User Code is entered.

(09)  24-hour Fire 

This sensor type is continuously armed 24-hours a day. A sensor programmed 
to this type will trigger the local alarm fi re sounder and the bell output regardless 
of the mode the system is in. Typical use would be for wireless smoke detectors. 
This sensor type is always active and cannot be bypassed.

(10)  Interior with Delay

This sensor type operates as a delayed sensor when the system is armed in the 
Away Mode, and when triggered, will start the Entry Delay #1 timer. If the system 
is armed in Away Mode with no Entry Delay (armed instant), this sensor type will 
trigger an instant alarm.

If the system is armed in Stay Mode (or Stay Mode with no Entry Delay), this 
sensor type will be bypassed.

(14)  24-hour Carbon Monoxide 

This sensor type is continuously armed 24-hours a day. A sensor programmed to 
this type will trigger the local alarm pulse sounder and the bell output regardless 
of the mode the system is in. Typical use would be for wireless carbon monoxide 
detectors. This sensor type is always active and cannot be bypassed.

(16)  24-hour Fire with Verifi cation 

This sensor type is continuously armed 24-hours a day. A sensor programmed to 
this type can trigger the local alarm fi re sounder and the bell output regardless 
of the mode the system is in. Typical use would be for wireless smoke detectors. 
This sensor type is always active and cannot be bypassed.

For verifi cation, this sensor type must be violated twice in two minutes, or remain 
violated for 30 seconds. If any other fi re sensor (verifi ed sensor type or not) 
violates within two minutes, both sensors will cause a fi re alarm.

(23)  No Response Type

This sensor type is a special zone that can be monitored for activity or inactivity 
by the Central Station. It does not affect security system status.

(24)  Silent Burglary

This sensor type is for silent triggering the burglary alarm with perimeter doors 
and windows that will not be used to enter or exit the protected premises while 
the system is armed. The Control Panel’s sounder and the bell output will not 
activate.

An instant silent alarm will occur when this type of sensor is triggered with the 
system armed in either the Stay Mode or Away Mode.

† Indicates Sensor types that are not allowed for hardwired 
loops.

Содержание GO!control 2GIG-CNTRL2

Страница 1: ...Wireless Security System Installation Programming Instructions 2GIG CNTRL2 2GIG CP2...

Страница 2: ...e ceiling Do not install smoke alarms where normal ambient temperatures are above 100 F 37 8 C or below 40 F 4 C Also do not locate alarm in front of air conditioners heating registers or other locati...

Страница 3: ...ounder Disable Icon 14 Backup Battery Status Icon 14 Test Mode Icon 14 Touch Screen Keypad Traffic Icon 14 GSM Radio Icon 14 Interior Sensor Open Icon 14 Programming Navigation 15 Navigation Arrows Go...

Страница 4: ...requirements to qualify for a discount For an ETL smoke alarm system use only approved model smoke detectors with this Control Panel NOTE Some cities and municipalities may require an alarm system per...

Страница 5: ...subscribers can query and control their system using a computer browser from anywhere in the world The Alarm com server can also send messages time corrections and software updates to the Control Pan...

Страница 6: ...lashes ORANGE when ANY sensor is open not ready to arm Flashes RED while system is armed HOME BUTTON INDICATOR THIRD HAND HANGER STRAP Hooks onto mounting plate during installation to hold the Control...

Страница 7: ...ery connector into the connector on the Control Panel s circuit board 14 Swing the Control Panel up placing the bottom over the lip of the mounting bracket Push the top of the Control Panel into the m...

Страница 8: ...second button lockout Lithium battery 345 MHz ETL Listed 2GIG GB1 Glass Break Detector Monitors for the sound of breaking glass Two test LEDs Dual shatter recognition technology thud then crash Lithiu...

Страница 9: ...module Locking connector 2GIG ANT4X External In wall GSM Antenna Antenna installs in the wall behind Control Panel 2 foot cable Plugs into GSM module Locking connector 2GIG BATT1 Standard Battery Pac...

Страница 10: ...rmally open N O or normally closed N C End of line resistors EOLR can also be used to supervise the loops Only contacts should be used with the hardwired loops The Control Panel does not support power...

Страница 11: ...LCO INPUT DROP SIDE OFTHE BOX OR ANY EARTH GROUNDS 3 At the demarcation box connect the RED cable wire to the box RING and the GREEN cable wire to the box TIP 4 At the demarcation box connect the BLAC...

Страница 12: ...as simply plug the antenna connector into the GSM module The antenna will drop into the wall or mount in the attic with the cable passing through the slot in the Control Panel s mounting plate See Fig...

Страница 13: ...ug the backup battery pack s connector into the connector on the Control Panel s circuit board The Control Panel will not recognize that the battery is connected until AC power is connected to the pow...

Страница 14: ...e displayed To arm the system without an entry delay un check the ENTRY DELAY check box To arm silently without sounding the Exit Delay beeps check the SILENT EXIT check box Stay Mode arming always ha...

Страница 15: ...shortcut to help the installer access the Installer Toolbox quickly Pressing the lower right corner of the Home Screen while the system is disarmed will immediately display a code entry screen When t...

Страница 16: ...he system is being tested in Walk Test Mode the test mode icon will be displayed on the status bar Touch Screen KeypadTraffic Icon When the Control Panel is communicating to a touch screen keypad the...

Страница 17: ...utton advances to the next programming question section The arrows select the next or previous programming sub question The arrows choose values for the question or move the cursor left and right alon...

Страница 18: ...allation The volume setting DOES NOT affect the volume of alarm sounds 9 Press to view the second toolbox screen 10 Press BACKLIGHTTIMEOUT and set the display lighting timeout 11 Press SET DATE and SE...

Страница 19: ...delay restart 0 1 1 enabled Q QUESTION DEFAULT Q 28 Select quick exit 0 1 1 enabled Q 29 Enter periodic test in days 0 255 30 days Q 31 Enter cancel time in minutes 5 255 5 minutes Q 32 Select cancel...

Страница 20: ...ion trouble report but not an alarm when the system is disarmed 06 24 hour Silent Alarm This sensor type is active independent of the system arming status The code for silent panic is sent to the Cent...

Страница 21: ...LAUNDRY 127 LEFT 128 LEVEL 129 LIBRARY 130 LIGHT 131 LIGHTS 132 LIQUOR 133 LIVING 134 LOADING 135 LOCK 136 LOFT 137 LOW WORD 138 MAIN 139 MAINTENANCE 140 MASTER 141 MEDICAL 142 MEDICINE 143 MENU 144 M...

Страница 22: ...umber 01 48 Sensor Type Exit entry perimeter interior etc Sensor Equipment Type Certain sensor types will ask for equipment type Sensor Equipment Code Sensor model door window PIR smoke detector etc S...

Страница 23: ...ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR insert PRESS...

Страница 24: ...arrows or enter the equipment type number directly on the keypad Select RF sensor equipment code DEFAULT 0000 other The equipment code is a 4 digit code that is assigned to the model of sensor being u...

Страница 25: ...button can be used to recall the last programmed sensor s serial number The sensor number will be filled in automatically if LEARN is used Select RF sensor dialer delay 0 1 DEFAULT Enabled 1 Required...

Страница 26: ...announcement and chime options for the sensor Wired Sensor Summary Screen After setting all the options for a sensor the wired sensor summary screen is displayed The screen can also be displayed for p...

Страница 27: ...ol Panel can be used with new or existing wired sensors If this wired sensor is new for the installation leave the default of new 0 If this wired sensor is already installed select existing 1 Select w...

Страница 28: ...button RF Key Fob Summary Screen After setting all the options for a sensor the key fob summary screen is displayed The screen can also be displayed for programmed key fobs during key fob program edit...

Страница 29: ...quipment age 0 1 DEFAULT New 0 The Control Panel can be used with new or existing key fobs If this fob is new for the installation leave the default of new 0 If this fob is already installed select ex...

Страница 30: ...een After setting all the options for a sensor the RF keypad summary screen is displayed The screen can also be displayed for programmed RF keypads during RF keypad program editing by pressing the SUM...

Страница 31: ...the Control Panel will learn the RF keypad s serial number TS1 WirelessTouch Screen Keypads For 2GIG TS1 Wireless Touch Screen Keypads press LEARN The Control Panel will display Pair with TS 1 Initia...

Страница 32: ...HIFT button accesses the pound and star symbols The P button adds a 3 second pause to the dialing NOTE If a second Central Station telephone number is programmed with question Q 41 the Control Panel w...

Страница 33: ...e supervised If the wiring to the sounder is cut for 15 30 or 45 seconds a bell trouble report can be sent to the Central Station The default 0 disables external sounder supervision To supervise the e...

Страница 34: ...information on setting the cancel report trigger time NOTE This default can be changed without affecting SIA CP 01 compliance Q 33 Select cross sensor 47 48 0 1 DEFAULT Disabled 0 The Control Panel c...

Страница 35: ...sses B C D E and F characters Q 42 Select remote control phone 0 3 DEFAULT Data and voice 3 This setting controls remote telephone access to the system The data option is for the installer It allows a...

Страница 36: ...trouble beeps from sounding from 10 pm to 9 am The trouble s will still be displayed and immediately reported to the Central Station and can be acknowledged but they won t sound beeps until after 9 a...

Страница 37: ...shutdown until the time of disarm and the sensor is closed The default 0 prevents alarm restore reports To allow alarm restore reports select enabled 1 Q 58 Select trouble restore reports to CS 0 1 DE...

Страница 38: ...light saving end week Q 71 Select system tamper causes trouble 0 1 DEFAULT Enabled 1 The Control Panel s case has a tamper switch that detects if the case has been opened The system can be programmed...

Страница 39: ...isible 1 The Z Wave home services feature can be enabled or disabled with various remote control access options The default 1 displays the SERVICES button but will show a message that the feature is c...

Страница 40: ...1 DEFAULT Disabled 0 This setting enhances system operation in personal emergency applications and also provides the dealer with the option of the siren sounding until the bell cut off or to the end...

Страница 41: ...permitted 4 Setup each User Code with the User Access Option Screen Each User Code can be set to be currently valid or not or to have conditional validity depending on a time and date schedule Refer...

Страница 42: ...ome active again To re enable the sounder manually follow these steps 1 From the Installer Toolbox Screen press ENABLE SOUNDER 2 A confirmation screen will be displayed Press OK Zone ReportingTest To...

Страница 43: ...est report to the Central Station Exiting the Walk Test Mode will send a stop test report to the Central Station To perform a walk test follow these steps 1 From the Installer Toolbox screen press WAL...

Страница 44: ...Installer Toolbox TelephoneTest The telephone test checks the land line connection to the Central Station through the Control Panel s built in digital communicator The test is accessed through the Us...

Страница 45: ...s Industry Canada Notices NOTICE The ringer equivalence number REN assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone int...

Страница 46: ...exit delay restart 0 1 1 enabled Q QUESTION DEFAULT Q 28 Select quick exit 0 1 1 enabled Q 29 Enter periodic test in days 0 255 30 days Q 31 Enter cancel time in minutes 5 255 5 minutes Q 32 Select c...

Страница 47: ...126 LAUNDRY 127 LEFT 128 LEVEL 129 LIBRARY 130 LIGHT 131 LIGHTS 132 LIQUOR 133 LIVING 134 LOADING 135 LOCK 136 LOFT 137 LOW WORD 138 MAIN 139 MAINTENANCE 140 MASTER 141 MEDICAL 142 MEDICINE 143 MENU...

Страница 48: ...46 Notes...

Страница 49: ...47 Notes...

Страница 50: ...panel internal features 4 Control panel location 5 Control panel location height 5 Control panel mounting 11 Control panel mounting plate 8 Control panel wiring 11 Control panel wiring diagram 2 Cross...

Страница 51: ...31X telephone jack 9 S Saving programming 39 Security screen 12 Select keyfob remote arming mode on system not ready 38 Select siren mode 38 Sensor signal loss through materials 5 Sensor types 18 Sens...

Страница 52: ...v1 9 233497 E Copyright 2012...

Отзывы: