background image

Gateway Instruction

You can request your Ethernet or LTE gateway by visiting 

Zurn.com/plumbsmart-gateway-request

or call Zurn Customer Care at 1-844-987-6737

Step 1. Request Gateway:

Step 2. Cabling, Powering and Connecting Your Device:

1. 

Connect one end of the RJ45 Ethernet cable (supplied) to the 

gateway’s Ethernet port and plug the cable’s other end into the 

nearest wall port of the building’s Ethernet network.

2. 

Connect the power supply to the power jack.

3. Wait for status LED to go from ON to double flash every second, 

the LoRa LED to turn ON solid, and the cell LED (if LTE enabled) 

to flash once every 3 seconds. Should take around 1-2 minutes 

depending on location. Your gateway is now ready to transmit 

data from your Zurn connected product.

4. Zurn  Gateways  have  been  set  to  DHCP  by  default.  Please 

consult local IT support for possible additional access 

requirements for your network.

Step 3. Determining general Location for the Zurn Gateway:

•  Select a location central to all devices to be connected to this 

gateway. Place the gateway as high as possible, such as near 

the top of a wall.

• 

Avoid  obstructions. Thick  walls  and  reflective  surfaces,  such 

as metal, weaken the signal between the gateway and other 

devices.

• 

The LoRa antenna is an omni-directional antenna, but for best 

results, mount the device so the LoRa antenna is in a vertical 

position near the top of a wall. We recommend conducting a site 

survey to test the signal strength in different locations before 

you mount the device.

Step 4. Mounting the Zurn Gateway:

The device ships with a mounting bracket. You will also need:

• 

Four #6 screws with anchors 

•  Screwdriver 
• 

Drill

1. 

Determine where you want to mount the device.

2. 

Mark where you want the screws to go.

3. Drill holes for the screws and insert anchors.
4. Place the mounting bracket and secure it with screws.

5. 

Attach the device to the bracket and rotate to lock into place.

Register in plumbSMART

NOTE:  Instructions below are duplicated from registration card supplied with monitor

1.  Install Zurn Connected Product(s)

2. 

Install Zurn Gateway per the Gateway Instructions Manual

3.  Request plumbSMART Administrator Account at 844-987-6737

4.  Zurn creates your Enterprise Account for you! (You will be required to identify your building location, number of floors, and number 

of rooms.)

5. 

Log in to plumbsmart.zurn.com

6.  Register each Connected Product in plumbSMART (Watch How-To Videos to Get Started. Located in the support section inside the 

portal.)

7.  Now, Relax.  You’re Connected.

Summary of Contents for AquaSense ZER-W2 Series

Page 1: ... and use the purchaser shall determine the suitability of the product for his intended use and the purchaser assumes all risk and liability whatever in connection therewith Where permitted by law the implied warranty of merchantability is expressly excluded If the products sold hereunder are consumer products the implied warranty of merchantability is limited to a period of three years and shall b...

Page 2: ...mmunications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase t...

Page 3: ...r than this measurement Deburr by chamfering O D and I D of end of water supply pipe NOTE Before installation turn off water supplies to existing fixture and remove flushometer if replacing an existing device Finished Wall Water Supply Pipe Center Line of Fixture Spud 11 4 Sweat Solder Adapter Set Screw Chrome Cover Tube Wall Escutcheon Distance to Measure 2 Slide threaded sweat solder adapter ont...

Page 4: ... to control stop inspect and verify that the O ring seal is located within the O ring groove at the tailpiece Ensure that the locking nut and locking snap ring are also present on the tailpiece Flush Valve Installation Instructions Lubricate O ring with water if necessary and insert flush valve tailpiece into the control stop valve Tighten locking nut using a smooth jawed wrench Vacuum Breaker Tub...

Page 5: ...e adjustment of the activation distance see Appendix A Adjusting Your E Z Flush The E Z Flush unit has a 10 minute start up sequence in which the Object Lock Sensor will flash the User In View yellow L E D continuously as long as a user is in view After the start up sequence is completed and when the Object Lock Sensor has a user in view the User In View yellow L E D will flash only 3 times after ...

Page 6: ... valve shown on the right 3 Replace the plastic cover and main body cover without reinstall ing the working parts 4 Open the stop valve by using the stop adjusting screw and flush out all debris from pipe and connections 5 Shut stop open cover reinstall the working parts replace both covers and tighten This procedure should also be repeated when the system is drained for seasonal use as occurs in ...

Page 7: ...esired activation distance 6 Use sensor adjustor tool and turn Distance Adjustment Screw all the way down and then turn slowly up until yellow L E D begins to flash 7 Ensure Object Lock Sensor is not detecting stall door or wall by closing door stepping out of sensor path and making sure yellow L E D is not flashing If sensor locks onto door or wall unit will not flush properly Shorten activation ...

Page 8: ...faces such as metal weaken the signal between the gateway and other devices The LoRa antenna is an omni directional antenna but for best results mount the device so the LoRa antenna is in a vertical position near the top of a wall We recommend conducting a site survey to test the signal strength in different locations before you mount the device Step 4 Mounting the Zurn Gateway The device ships wi...

Page 9: ...eries are dead Replace batteries If the E Z Flush does not begin to function call Cus tomer Service at 1 800 997 3876 Flush Valve Trouble Shooting Guide Problem Corrective Action Status Good posted in plumbSMART and faucet actuation event data not appearing in plumbSMART 2 hours or Device Not Communicating warning or severe alert posted in plumbSMART for all devices 3 hours Step 1 Verify gateway S...

Page 10: ...aucet actuator electronics Restore proper electrical connection as needed Step 2 Test activate the faucet If problem persists see Faucet Troubleshooting section in this guide for other steps Status Good posted in plumbSMART and faucet actuates but usage event data not appearing in plumbSMART Charts Step 1 Verify gateway is powered and LoRa Status LED is ON If not apply power per Zurn Gateway Insta...

Page 11: ...t 1 0 gal flush P6000 EUA WS1 Water Saving Urinal Kit 1 5 gal flush P6000 EUA WS Full Flush Urinal Kit 3 0 gal flush P6000 EUA FF Repair Parts Inside Parts Product No Urinal Relief Valve Item 12 P6000 EU13 Closet Relief Valve Item 12 P6000 EC13 Flush Connections and Spud Coupling Kits Product No Flush Tube Assembly for Flush Valves Includes Items 15 19 Specify Diameter and Length P6000 A Vacuum Br...

Page 12: ...STRIES LLC 511 W Freshwater Way Milwaukee WI U S A 53204 Ph 1 855 ONE ZURN Fax 919 775 3541 In Canada ZURN INDUSTRIES LIMITED 7900 Goreway Drive Unit 10 Brampton Ontario L6T 5W6 Ph 905 405 8272 Fax 905 405 1292 Rev A Date 11 10 20 C N No NEW Prod Dwg No FV746 ...