PROBLEM 

CAUSE

SOLUTION

  

Yellow L.E.D. light flashes 3 times 

when there are no

users.

Front of Object Lock Sensor is

covered or Object Lock Sensor is

set too far out, registering the

opposite wall or door as a user.

Remove item covering sensor or 

adjust Object Lock Sensor activation 

distance.  (See Appendix B – Adjust

-

ing the E-Z Flush.)

Yellow L.E.D. light flashes continuous

-

ly when Object

Lock Sensor is activated by a user.

E-Z Flush unit is in 10-minute

start-up mode (when first activated), or 

Sensor Range Reset

Button has been depressed.

Yellow L.E.D. light will flash only 3 

times, acknowledging a user is in view 

after the 10-minute start-up mode.

Red L.E.D. light flashes.

Batteries need replacing.

Replace batteries.

Not enough water to fixture or too 

much water to fixture.

Diaphragm damaged or valve

control stop improperly adjusted.

Replace diaphragm and/or adjust 

valve control stop.

Valve will not operate.

Object Lock Sensor range set too

close to E-Z Flush, batteries are

dead, or water supply is turned off.

Adjust Object Lock Sensor, replace 

batteries, or turn water on. If the E-Z 

Flush does not begin to function, call 

Customer Service at 1-800-997-3876.

Valve does not shut off.

Dirt or debris preventing diaphragm 

from functioning properly.

Remove dirt or debris, check by-pass 

hole in diaphragm.

Valve does not flush even after Object 

Lock Sensor has been adjusted.

Batteries are dead.

Replace batteries. If the E-Z Flush 

does not begin to function, call Cus-

tomer Service at 1-800-997-3876.

Flush Valve Trouble Shooting Guide

Problem

Corrective Action

“Status – Good” posted in plumbSMART and faucet actuation 

event data not appearing in plumbSMART (< 2 hours) or 

“Device Not Communicating” warning or severe alert posted in 

plumbSMART for all devices (> 3 hours)

Step 1

Verify gateway Status LED flashes twice every 2 seconds.  If LED 

is OFF or ON solid, power cycle the gateway and wait for no 

more than 5 minutes for unit to initialize and connect.

Step 2

After initialization is finished, LORA LED should turn ON solid 

within an additional minute.

Step 3 

If LORA LED does not turn ON solid and ethernet cable 

connected, contact facility IT administrator to modify port rules 

to allow Zurn gateway to access the internet via local router.  

If gateway model is ETH/LTE, visually verify SIM card is installed 

in designated slot on the side of gateway.  If unit has a SIM card, 

then disconnect ethernet cable and power cycle the gateway 

and wait for unit to initialize and connect.  LORA LED should 

turn ON solid after initialization.

Step 4

If problem still present, move gateway closer to LoRa monitors 

and/or verify gateway mounting, orientation and connections 

comply with requirements listed in Zurn Gateway Installation 

Guide.

Contact Zurn Customer Service at 1.855.ONE.ZURN 

(1.855.663.9876) for assistance with additional troubleshooting 

steps.

Trouble Shooting: Gateway

For further assistance with troubleshooting, visit https://plumbsmart.zurn.com/app/training

Summary of Contents for AquaSense ZER-W2 Series

Page 1: ... and use the purchaser shall determine the suitability of the product for his intended use and the purchaser assumes all risk and liability whatever in connection therewith Where permitted by law the implied warranty of merchantability is expressly excluded If the products sold hereunder are consumer products the implied warranty of merchantability is limited to a period of three years and shall b...

Page 2: ...mmunications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase t...

Page 3: ...r than this measurement Deburr by chamfering O D and I D of end of water supply pipe NOTE Before installation turn off water supplies to existing fixture and remove flushometer if replacing an existing device Finished Wall Water Supply Pipe Center Line of Fixture Spud 11 4 Sweat Solder Adapter Set Screw Chrome Cover Tube Wall Escutcheon Distance to Measure 2 Slide threaded sweat solder adapter ont...

Page 4: ... to control stop inspect and verify that the O ring seal is located within the O ring groove at the tailpiece Ensure that the locking nut and locking snap ring are also present on the tailpiece Flush Valve Installation Instructions Lubricate O ring with water if necessary and insert flush valve tailpiece into the control stop valve Tighten locking nut using a smooth jawed wrench Vacuum Breaker Tub...

Page 5: ...e adjustment of the activation distance see Appendix A Adjusting Your E Z Flush The E Z Flush unit has a 10 minute start up sequence in which the Object Lock Sensor will flash the User In View yellow L E D continuously as long as a user is in view After the start up sequence is completed and when the Object Lock Sensor has a user in view the User In View yellow L E D will flash only 3 times after ...

Page 6: ... valve shown on the right 3 Replace the plastic cover and main body cover without reinstall ing the working parts 4 Open the stop valve by using the stop adjusting screw and flush out all debris from pipe and connections 5 Shut stop open cover reinstall the working parts replace both covers and tighten This procedure should also be repeated when the system is drained for seasonal use as occurs in ...

Page 7: ...esired activation distance 6 Use sensor adjustor tool and turn Distance Adjustment Screw all the way down and then turn slowly up until yellow L E D begins to flash 7 Ensure Object Lock Sensor is not detecting stall door or wall by closing door stepping out of sensor path and making sure yellow L E D is not flashing If sensor locks onto door or wall unit will not flush properly Shorten activation ...

Page 8: ...faces such as metal weaken the signal between the gateway and other devices The LoRa antenna is an omni directional antenna but for best results mount the device so the LoRa antenna is in a vertical position near the top of a wall We recommend conducting a site survey to test the signal strength in different locations before you mount the device Step 4 Mounting the Zurn Gateway The device ships wi...

Page 9: ...eries are dead Replace batteries If the E Z Flush does not begin to function call Cus tomer Service at 1 800 997 3876 Flush Valve Trouble Shooting Guide Problem Corrective Action Status Good posted in plumbSMART and faucet actuation event data not appearing in plumbSMART 2 hours or Device Not Communicating warning or severe alert posted in plumbSMART for all devices 3 hours Step 1 Verify gateway S...

Page 10: ...aucet actuator electronics Restore proper electrical connection as needed Step 2 Test activate the faucet If problem persists see Faucet Troubleshooting section in this guide for other steps Status Good posted in plumbSMART and faucet actuates but usage event data not appearing in plumbSMART Charts Step 1 Verify gateway is powered and LoRa Status LED is ON If not apply power per Zurn Gateway Insta...

Page 11: ...t 1 0 gal flush P6000 EUA WS1 Water Saving Urinal Kit 1 5 gal flush P6000 EUA WS Full Flush Urinal Kit 3 0 gal flush P6000 EUA FF Repair Parts Inside Parts Product No Urinal Relief Valve Item 12 P6000 EU13 Closet Relief Valve Item 12 P6000 EC13 Flush Connections and Spud Coupling Kits Product No Flush Tube Assembly for Flush Valves Includes Items 15 19 Specify Diameter and Length P6000 A Vacuum Br...

Page 12: ...STRIES LLC 511 W Freshwater Way Milwaukee WI U S A 53204 Ph 1 855 ONE ZURN Fax 919 775 3541 In Canada ZURN INDUSTRIES LIMITED 7900 Goreway Drive Unit 10 Brampton Ontario L6T 5W6 Ph 905 405 8272 Fax 905 405 1292 Rev A Date 11 10 20 C N No NEW Prod Dwg No FV746 ...

Reviews: