Chapter 1 Introduction to Cluster
Note:
If the altitude is below 1800m, the long-term operating temperature is 40°C and the
short-term operating temperature is 50°C.
If the altitude is above 1800m, the maximum temperature of the operating environment
decreases by 0.5°C for every 100-meter increase in altitude. The maximum supported
altitude is 5000m.
Physical Parameters of a Central Switching Shelf
For the parameters of a central switching shelf of the ZXR10 T8000 cluster system, see
Table 1-2
.
Table 1-2 Physical Parameters of a Central Switching Shelf of the ZXR10 T8000 Cluster
System
Physical Parameter
ZXR10 T8000
Size (Width x Height x Depth)
442mm x 1686mm x 740mm
Shelf (including backplane)
64kg
Weight
Full configuration
240kg
Total number of slots
22
Number of MPU slots
2
Number of CSFU slots
16
Number of slots
Number of CESU slots
4
Switching capacity
Per machine
7.68Tbps
Backup mode
1+1
Rated power per machine
5100W
Rated voltage
-48V
Maximum voltage range
-60V - -40V
Rated input current
75A/channel (for 2 subarea power supply)
DC power supply
Air circuit breaker
100A (full configuration, supporting 2
subarea power supply)
1-7
SJ-20110901170352-005|2011-10-15 (R2.0)