CR-U* Compound-Filled Cable Gland
– ASSEMBLY INSTRUCTIONS FOR SAFE USE
Where cable gland CR-U* is used customer is obliged to follow the following instructions
with sealing individual cable cores when connecting the actuator.
Brief Description
The Peppers CR-U* type Compound-filled cable gland is for outdoor use in the appropriate Hazardous Areas
with unarmoured cable of any construction, with or without braids or screens, where the braids or screens pass
trough the compound. A variant giving electrical continuity to a lead sheath is available. It gives environmental
protection to IP 68 and Deluge.
Warning:
PLEASE STUDY CAREFULLY THESE INSTRUCTIONS BEFORE INSTALLATION. These glands should not be
used in any application other than those mentioned here or in Peppers Data Sheets, unless Peppers states in writing
that the product is suitable for such application. Peppers can take no responsibility for any damage, injury or other
consequential loss caused where the glands are not installed or used according to these instructions. This leaflet is not
intended to advise on the selection of cable glands. Further guidance can be found in the standards listed below.
STEP-BY-STEP FITTING INSTRUCTIONS
1. Split gland as shown in the figure.
2. Fit Entry Body. Hand-tighten, then using wrench tighten a further 1/2 turn. DO NOT EXCEED MAX TORQUE FOR
ENCLOSURE.
3. Slide Rear Assembly (locking nut, central enclosure and cap nut) onto cable as shown in the figure.
4. CABLE PREPARATION
Strip jacket so that cores are fully exposed in the compound chamber, length to suit installation. Lead sheath must
be cut to push through the continuity washer. Remove protective foils, and any cords/fillers from around and between
the cores. Take care not to cut the insulating sleeves of the cores. Pigtail and sleeve any screens to be passed
through compound.
15
CR-U* Compound-Filled Cable Gland
- ASSEMBLY INSTRUCTIONS FOR SAFE USE
Where cable gland CR-U* is used customer is obliged to follow the following instructions
with sealing individual cable cores when connecting the actuator.
Brief Description
The Peppers CR-U* type Compound-filled cable gland is for outdoor use in the appropriate Hazardous Areas with unar-
moured cable of any construction, with or without braids or screens, where the braids or screens pass trough the compound.
A variant giving electrical continuity to a lead sheath is available. It gives environmental protection to IP 66, IP 68 and Deluge.
Warning:
PLEASE STUDY CAREFULLY THESE INSTRUCTIONS BEFORE INSTALLATION. These glands should not be
used in any application other than those mentioned here or in Peppers Data Sheets, unless Peppers states in writing
that the product is suitable for such application. Peppers can take no responsibility for any damage, injury or other
consequential loss caused where the glands are not installed or used according to these instructions. This leaflet is
not intended to advise on the selection of cable glands. Further guidance can be found in the standards listed below.
STEP-BY-STEP FITTING INSTRUCTIONS
1. Split gland as shown.
2. Fit Entry Body. Hand-tighten, then using wrench tighten a further 1/2 turn. DO NOT EXCEED MAX TORQUE FOR
ENCLOSURE.
3. Slide Rear Assembly
(Back Nut, Mid Cap and Union Nut)
onto cable as shown.
4. CABLE PREPARATION
Strip jacket so that cores are fully exposed in the compound chamber, length to suit installation. Lead sheath must be
cut to push through the continuity washer. Remove protective foils, and any cords/fillers from around and between the
cores. Take care not to cut the insulating sleeves of the cores. Pigtail and sleeve any screens to be passed through
compound.
ZADNÍ
SESTAVA
MONTÁŽNÍ NÁVOD PO JEDNOTLIVÝCH KROCÍCH
Protimatice
ROZDĚLENÍ
VÝVODKY
P
ŘÍPRAVA
K
ABELU
STLAČENÍ TĚSNICÍ HMOTY
V
YTLAČENÍ TĚSNICÍ
HMOTY
DOKONČENÁ MONTÁŽ
Středový
uzávěr
Převlečná matice
Vstupní
díl
U
A
Velikost
vývodky
élka
těsnicí
hmoty
O
lověný plášť
K
ontinuální t ěsnění
(
typ CR-U2* )
Continuity washer
(CR-U2* types)
Back nut
Union nut
SPLIT GLAND
REAR ASSEMBLY
STEP-BY-STEP FITTING INSTRUCTIONS
COMPLETED INSTALLATION
CABLE
PREPARATION
COMPOUND
EXTRUSION
COMPOUND PACKING
Entry
body
Gland
size
TABLE 1
Compound
lenght
Mid cap
Lead sheath