Preinstallation Information

Electrical Data

 1

.  Check to be sure your power source is capable of handling the voltage require-

ments of the motor, as indicated on the pump nameplate. 

 2.  

The installation of pumps using auxiliary variable level float switches is the 

responsibility of the installing party and care should be taken that the tethered 

float switch will not hang up on the pump apparatus or pit peculiarities and is 

secured so that the pump will shut off.  It is recommended that rigid piping and 

fittings be used and the pit be 36” (91.4 cm) or larger in diameter.   

                        

 3.  INFORMATION - VENT HOLE PURPOSE.

 It is necessary that all submersible 

pumps capable of handling various sizes of solid waste be of the bottom intake 

design to reduce clogging and seal failures. If a check valve is incorporated in the 

installation, a vent hole [approx. 3/16” (4 mm)] must be drilled in the discharge 

pipe below the check valve and pit cover to purge the unit of trapped air. Water 

stream will be visible from this hole during pump run periods. This vent hole 

should be checked periodically for clogging and cleaned as necessary. Trapped 

air is caused by agitation and/or a dry basin. 

 4.

  Water hammer creates momentary high pressure surges. These surges can 

cause severe damage to check valves and the piping system. Consideration for 

water hammer must be included in the piping system design. Reference ASPE 

Data Book, Chapter 2.33. Some systems may require external spring or lever 

weighted check valves or other engineered solutions.

 5.

  Three phase pumps must be connected for proper rotation, which is counter-

clockwise looking into impeller inlet. See page 4 for instructions for checking 3 

phase rotation.

1.    Inspect your pump.

 Occasionally, products are damaged during shipment. If the unit is damaged, contact your dealer before using. 

DO NOT 

remove the test plugs in 

the cover nor the motor housing. 

 

                        

2.    Carefully read the literature

 provided to familiarize yourself with specific details regarding installation and use. These materials should be retained for future refer

ence.

 1. 

Do not lift, carry, or hang pump by the electrical cables. Damage to the electrical 

cables can cause shock, burns or death.   

                        

 2. Make sure there is a properly grounded connection available.

  All pumps are 

furnished with provisions for proper grounding to help protect you against the pos-

sibility of electrical shock.   

                        

 3.

 

 

Make certain that the control box is within the reach of the pump’s power supply cord. 

DO NOT USE AN EXTENSION CORD.

 Extension cords that are too long or too light 

do not deliver sufficient voltage to the pump motor. But, more importantly, they could 

present a safety hazard if the insulation were to become damaged or the connection 

end were to fall into the sump.

 4.  Make sure the pump electrical supply circuit is equipped with fuses and disconnect 

or circuit breakers of proper capacity. 

A separate branch circuit is recommended, 

sized according to the “National Electrical Code” for the current shown on the pump 

nameplate.

 5.

  Care should be taken during the initial installation to be sure that adequate 

air supply is available whenever any person is in the basin. Always follow OSHA 

guidelines on confined space requirements.

 

6.

 Risk of electric shock - These pumps have not been investigated for use in swimming 

pool areas.

NOTE: Pumps with the “UL” mark and pumps with the “US” mark are tested to UL Standard 

UL778. CSA Certified pumps are certified to CSA Standard C22.2 No. 108.

CAUTION

SEE BELOW FOR

LIST OF CAUTIONS

SEE BELOW FOR

LIST OF WARNINGS

Model

HP

Service

Factor

RPM

Voltage Phase

Hertz

Amps

KVA 

Code

Winding 

Resistance 

Line-to-Line

Full Load

In Air

Shut Off Locked Rotor

E611

1

1.2

1750

230

1

60

6.9

4.1

4.7

48.0

M

2.5 / 4.8

J611

1

1.2

1750

200

3

60

4.8

3.3

3.7

32.0

M

2.2

F611

1

1.2

1750

230

3

60

4.2

2.2

2.6

28.0

M

3

G611

1

1.2

1750

460

3

60

2.1

1.1

1.3

14.0

M

12

BA611

1

1.2

1750

575

3

60

1.7

1.0

1.1

11.5

M

18

E621

1-1/2

1.2

1750

230

1

60

8.9

4.3

5.3

48.0

J

2.5 / 4.8

J621

1-1/2

1.2

1750

200

3

60

5.9

3.3

3.7

32.0

J

2.2

F621

1-1/2

1.2

1750

230

3

60

5.1

2.3

2.9

28.0

J

3

G621

1-1/2

1.2

1750

460

3

60

2.6

1.2

1.5

14.0

J

12

BA621

1-1/2

1.2

1750

575

3

60

2.0

1.0

1.3

11.5

J

18

E631

2

1.2

1750

230

1

60

14.5

7.2

8.0

86.0

L

0.94 / 3.8

J631

2

1.2

1750

200

3

60

7.8

4.5

5.0

46.0

J

1.5

F631

2

1.2

1750

230

3

60

6.8

2.3

4.4

41.0

K

2

G631

2

1.2

1750

460

3

60

3.4

1.2

2.2

20.5

K

8

BA631

2

1.2

1750

575

3

60

2.7

1.4

1.8

16.2

K

12

E641

3

1.2

1750

230

1

60

17.0

7.2

8.9

86.0

H

0.94 / 3.8

J641

3

1.2

1750

200

3

60

11.0

4.5

5.6

46.0

F

1.5

F641

3

1.2

1750

230

3

60

9.6

2.3

4.7

41.0

F

2

G641

3

1.2

1750

460

3

60

4.8

1.7

2.4

20.5

F

8

BA641

3

1.2

1750

575

3

60

3.9

1.4

2.0

16.2

F

12

E651

5

1.2

1750

230

1

60

28.0

16.1

19.7

139.0

H

0.9 / 3.1

J651

5

1.2

1750

200

3

60

17.5

6.1

7.6

64.0

D

1

F651

5

1.2

1750

230

3

60

15.2

6.1

7.4

58.0

E

1.3

G651

5

1.2

1750

460

3

60

7.6

3.1

3.7

29.0

E

5.2

BA651

5

1.2

1750

575

3

60

6.1

1.5

3.4

23.0

E

8

J661

7-1/2

1.0

1750

200

3

60

25.3

17.9

18.3

83.0

C

0.5

F661

7-1/2

1.0

1750

230

3

60

22.0

15.0

15.7

72.0

C

0.7

G661

7-1/2

1.0

1750

460

3

60

11.0

7.5

7.9

36.0

C

2.8

BA661

7-1/2

1.0

1750

575

3

60

9.0

5.3

5.8

29.0

C

5.4

© Copyright 2017 Zoeller

®

 Co. All rights reserved.

Summary of Contents for 611

Page 1: ...pairmanualon600Seriespumps Shouldfurtherassistancebe necessary please call our Product Support Department at 1 800 928 PUMP 7867 Table of Contents Safety Instructions 1 Limited Warranty 2 Performance Data 2 Preinstallation Information 3 Electrical Data 3 Typical Dewatering Installation 4 Typical Sewage Installation 4 Pump Wiring Instructions 5 6 Operation 6 7 Maintenance 7 Service Checklist 8 Safe...

Page 2: ...bjected to misuse misapplication neglect alteration accident or act of nature that has not been installed operated or maintained in accordance with Manufacturer s installation instructions that has been exposed to outside sub stances including but not limited to the following sand gravel cement mud tar hydrocarbons hydrocarbonderivatives oil gasoline solvents etc orother abrasive or corrosive subs...

Page 3: ...USE AN EXTENSION CORD Extension cords that are too long or too light do not deliver sufficient voltage to the pump motor But more importantly they could present a safety hazard if the insulation were to become damaged or the connection end were to fall into the sump 4 Makesurethepumpelectricalsupplycircuitisequippedwithfusesanddisconnect or circuit breakers of proper capacity A separate branch cir...

Page 4: ...mp housing Be sure that this hole is cleared during any servicing 7 Vent gases and odors to the atmosphere through vent pipe per Local and State codes 8 Secure power cord to avoid entanglement with variable level float switch mechanism 9 Do not reduce pump discharge pipe below 3 76 mm IPS size 10 Basin must be in accordance with all applicable codes and specifications Basin must be sized to allow ...

Page 5: ...ave provisions for mounting these starting compo nents 2 All pumps require overload protection in panel Use with approved motor control that matches motor input in full load amperes with overload element s selected or adjusted in accordance with control instructions 3 Hazardous Location pumps require panels that offer intrinsically safe relays and all other NEC requirements must be followed see Ar...

Page 6: ...g the terminal ends of wire leads Single Phase Installation All single phase models require start capacitor run capacitor and relay in the circuit to start and operate properly These components can be purchased separately or prewired in Zoeller Pump Company control panel For components purchased separately used the diagram for installation and hookup Singlephasemodelsarenonautomatic Tooperateautom...

Page 7: ... should be wearing a harness with safety rope extending to the surface so that they can be pulled out in case of asphyxiation Sewage water gives off methane and hydrogen sulfide gases both of which can be highly poisonous Installationandcheckingofelectricalcircuitsandhardwareshouldbeperformed by a qualified electrician Pump is never to be lifted by power cord Unit must be flushed and disinfected i...

Page 8: ...ch Float travel obstructed Defective or damaged float switch Magnetic starter contacts shorted Air lock check vent hole E Pump operates but delivers little or no water Check for plugged Pump housing discharge pipe or sticking check valve Vent hole clogged or not drilled Discharge head exceeds pumps capacity Low or incorrect voltage Incorrect motor rotation Defective capacitor F Drop in head and or...

Page 9: ...oeller Pump Company http reg zoellerpumps com Número de modelo ___________ Código de fecha __________ Número de serie Bomba 1 ____________ Bomba 2 ___________ Simplex N P de Panel ___________________________ Duplex N P de Sistema de riel ___________________ Nombre del trabajo _____________________________________ Distribuidor ___________________________________________ N S O Zoeller ______________...

Page 10: ...uehayasidoexpuestoa sustanciasforáneasqueincluyenperonoselimitanalosiguiente arena grava cemento lodo alquitrán hidrocarburos derivados de hidrocarburos aceite gasolina solventes etc u otras sustancias abrasivas o corrosivas toallas para lavar o productos sanitarios femeninos etc en todas las aplicaciones de bombeo Lagarantíapresentadaenelpárrafoanteriordejasinefectocualquier otra garantía expresa...

Page 11: ...os y que la cavidad sea de un diámetro de 91 4 cm 36 pulg o mayor 3 INFORMACIÓN FINALIDAD DEL RESPIRADERO Es necesario que todas las bombas sumergibles con capacidad para manejar desechos sólidos de diferentes tamaños tengan un diseño para entrada en la parte inferior de modo que se reduz can los atascos y las fallas del sello Si se incorpora una válvula de retención en la instalación deberá perfo...

Page 12: ... El agujero deberá estar debajo de la cubierta del contenedor y limpiarse periódicamente Durante los periodos de funcionamiento de la bomba se verá un chorro de agua que sale del respiradero Perfore también un respiradero en la caja de la bomba Asegúrese de que el respiradero no esté bloqueado durante el mantenimiento 7 Laventilacióndegasesyoloresquesalganporeltubodeventilación yseliberenhacialaat...

Page 13: ...erimientos de la NEC consulte los artículos 500 501 y 502 y los demás que correspondan Instrucciones de cableado Las bombas trifásicas no son automáticas Para su operación automática se requiere de un panel de control Siga las instrucciones del panel para cablear el sistema Antes de instalar una bomba revise la rotación de la bomba para asegurarse de que el cableado se haya conectado adecuadamente...

Page 14: ...ODELOS 631 641 651 Y 611 621 CON RELÉ GE DESPUÉS DEL 10 1 07 Rocíeunacapadeaceiteanticorrosivoalassuperficiesquenoesténpintadas Elimpulsordebegirarsecadaseismesesparamantenerlosselloslubricados y evitar que se queden pegados Si se va a almacenar el panel se recomienda lo siguiente Guarde el panel bajo techo siempre que sea posible y colóquelo en su empaque original Selle todas las aberturas Colóqu...

Page 15: ...és con una cuerda de seguridad que llegue hasta la super ficie para poder sacarlas en caso de asfixia Las aguas negras despiden gas metano y sulfuro de hidrógeno que pueden ser altamente tóxicos Lainstalaciónyrevisióndeloscircuitoseléctricosyelhardwaredeberáhacerla un electricista debidamente calificado Nunca levante la bomba jalándola del cable de alimentación ADVERTENCIA Antes de reparar se debe...

Page 16: ...ga o quema el fusible Voltaje incorecto Fuente de poder desbalanceada Rotación incorrecta del motor Carga baja o nagativa Temperatura del agua demasiado alta El impulsor o el sello están pegados mecánicamente Hay un defecto en el condensador o el regulador Hay un cortocircuito en el motor Se perdió una línea en la unidad trifásica C La bomba arranca y se detiene con demasiada frecuencia La válvula...

Page 17: ...es corporelles graves la mort ou des dommages matériels importants Il avertit des dangers qui PEUVENT causer des blessures corporelles graves la mort ou des dommages matériels importants Il avertit des dangers qui PEUVENT causer des blessures corporelles ou des dommages matériels IL AVERTIT DES CONSIGNES SPÉCIALES QUI SONT TRÈS IMPORTANTES ET QUI DOIVENT ÊTRE RESPECTÉES LIREMINUTIEUSEMENTTOUSLESAV...

Page 18: ...ace toutes les autres garanties expresses ou implicites et nous n autorisons aucun représentant ou autre personne à accepter la responsabilité en notre nom pour nos produits Prendre contact avec le Fabricant 3649 Cane Run Road Louisville KY40211 Attention Customer Support pour obtenir des réparations des pièces de remplacementoudesrenseignementssupplémentairesconcernantlagarantie LE FABRICANT REFU...

Page 19: ... 3 l faut vérifier que la prise est à portée du cordon d alimentation de la pompe NE PAS UTILISER DE RALLONGE Les rallonges trop longues ou de trop faible capacité ne fournissent pas la tension nécessaire au moteur de la pompe et elles peuvent être dangereuses si l isolant est endommagé ou si l extrémité avec le branchement tombe dans un endroit humide ou mouillé 4 Assurez vous que le circuit d al...

Page 20: ...e dispose d un trou d évent 7 Doit être nettoyé avant le etretien Les gaz et les odeurs rejetés dans l atmosphèreparletuyaud éventd aprèslescodeslocauxetnationaux 8 Sécuriser le cordon d alimentation afin d éviter son enchevêtrement avec le mécanisme de l interrupteur à flotteur à niveau variable 9 Ne pas utiliser un tuyau d évacuation de moins de 3 po IPS 10 La cuve doit être conforme aux codes e...

Page 21: ...ces nécessaires à l installation de ces composantes de démarrage 2 Toutes les pompes nécessitent une protection de surcharge dans le panneau N utiliser qu avec une commande moteur équivalente à l entrée du moteur en ampérage pleine charge incluant l élément les éléments de surcharge sélectionné s ou ajusté s selon les instruction de la commande 3 Les pompes pour emplacements dangereux nécessitent ...

Page 22: ...rmanente Installation monophasée Tous les modèles monophasés nécessitent un condensateur de démarrage un condensateur de fonctionnement et un relai dans le circuit afin de démarrer et de fonctionner correctement Ces composantes peuvent être achetées séparément ou être incluses dans le panneau de commande Zoeller Pump Company Suivre le schéma de câblage pour l installation et le branchement des com...

Page 23: ...ne qui peuvent tous les deux être fortement toxiques L installation et la vérification de l équipement électrique doivent être faites par un électricien qualifié Il ne faut jamais soulever la pompe par le cordon d alimentation AVERTISSEMENT Avantl entretien ilfautnettoyeretdésinfecterl unité àl intérieur comme à l extérieur INSPECTION GÉNÉRALE DU SYSTÈME Avant de mettre le système en marche un Rap...

Page 24: ...nce de blocage de l impulseur CAUSES FRÉQUENTES B Le moteur surchauffe et déclenche la surcharge ou grille un fusible Mauvaise tension Source d alimentation déséquilibrée Mauvaise rotation du moteur Pression faible ou négative Température de l eau excessive Blocage mécanique de l impulseur ou du joint Condensateur ou relais défectueux Court circuit du moteur Perte d une ligne dans une unité tripha...

Reviews: