MagnaPool™   |   Installation Manual

<

-FILTER PUMP

-AUX/LIGHTS

-PROGRAMMING

-LOW MODE

-SLAVE MODE

-REVERSING

-HELP MENU

-LANGUAGE

MAIN MENU

<

-BACKWASH

-SINGLE SPEED

-VARIABLE SPEED

FILTER PUMP

<

PLUGD TO DEVICE?

-YES

-NO

SINGLE SPEED

8.1.2

Variable Speed Filter Pump

1. The following pump models are compatible: 

FloPro™ VS, Flopro™ VS AUT

2.

Connect the filter pump to the controller at 

the VSP RS485 connection point in the low 

voltage raceway, see Table 5 and Figure 10 for 

wiring details.

3. Ensure the RS485 wires are in the proper order.

LOW VOLTAGE

HIGH VOLTAGE

RED

BL

K

YE

L

GRN

On the Controller

RED BL

K

YE

L

GRN

On the Pump

4. Ensure the pump DIP switches are in the 

correct position as follows:

1 = up 

2 = up 

3 = down 

4 = down 

5 = up

5. Press

.

6. Use

 to select “Filter Pump” 

then press  .

7. Use

 to select “Variable Speed” 

then press  .

8. The user interface will prompt “Variable Speed 

Plgd to Device”. Use 

 to select “Yes” 

then press  .

9. Use

 to select a speed then press  .

10. Use

 to adjust the RPM.

11. Once desired RPM is reached, press  .

12. Press

 to exit.

NOTE:

If multiple VSP timers have a time slot in common 

: it is the higher RPM that will be operated.

<

-FILTER PUMP

-AUX/LIGHTS

-PROGRAMMING

-LOW MODE

-SLAVE MODE

-REVERSING

-HELP MENU

-LANGUAGE

MAIN MENU

<

-BACKWASH

-SINGLE SPEED

-VARIABLE SPEED

FILTER PUMP

<

PLUGD TO DEVICE?

-YES

-NO

VARIABLE SPEED

<

VARIABLE SPEED

-SPEEDS

-MIN/MAX

-PRIMING

-PROGRAMMING

<

VSP SPEEDS

-RPM 1 1000

-RPM 2 1500

-RPM 3 2000

-RPM 4 2850

-QUICK  3450

8.1.3

Quick Clean

Quick Clean is a backwash mode is used to quickly 

start/stop the filter pump (single- or variable-speed 

pump) in order to backwash the filter. 
For variable speed pumps, the backwash RPM is 

set under “Quick”.
1.

Select YES to activate filtration.

2.

Select NO to stop filtration.

For safety reasons, the hydroxination is stopped 

during the backwash mode. To avoid emptying the 

pool, the backwash mode automatically stops after 

5 minutes. The variable speed pump RPM is by 

default set at 3450 rpm (max speed). This can be 

changed in the priming menu.

8.2

Aux/Lights

The hydroxinator is capable of controlling devices 

in addition to the filter pump. The equipment 

must be connected to the hydroxinator using the 

appropriate auxiliary line:
Aux 1: for equipment connected to the high voltage 

supply (230 V) (not applicable for Australia).
Aux 2: for equipment connected to the low voltage 

supply (12/24 V).
The following functions are available in the 

AUX/LIGHTS menu for auxiliaries 1 and 2:

●  Turn the equipment on/off

●  Program a timer (See section 8.7.6 for details)

For Australian products, in order to control 

the light transformer, an additional switching 

box is required. Please contact your local pool 

care professional for this relay box, item code 

WW000222.
1. Remove the lower cover from the housing.

2. Attach the 2 x core wires from the switch box 

to the terminal bar marked ‘AUX 2’.

3. Replace the cover/s.

4. Plug the switch box into any 

available 240V GPO.

5. Plug the light transformer directly into the 

socket located in the switch box. This will now 

control the light directly from the hydroxinator.

Summary of Contents for MagnaPool

Page 1: ...other local applicable regulations Before installing this product read and follow all warning notices and instructions that accompany this product Failure to follow warning notices and instructions m...

Page 2: ...he POD Kit 10 5 2 Drill the Pipe 10 5 3 Install the POD 10 5 4 Install the POD Cap 11 5 5 Install and Calibrate the Sensor s 11 5 6 Install the pH Down Intake and Injection lines 12 5 7 Calibration Pr...

Page 3: ...water temperatures are recommended for young children and when spa use exceeds 10 minutes b Since excessive water temperatures have a high potential for causing fetal damage during the early months o...

Page 4: ...lectric appliance such as a light telephone radio or television within 3 5 metres of a spa or hot tub The use of alcohol drugs or medication can greatly increase the risk of fatal hyperthermia in hot...

Page 5: ...et d Wall Mount Screws 7 mm X2 e Wall Mount Anchor X2 f Electrolytic Cell g Unions X2 h Glue on Adapter X2 i Adapter O Rings X2 j Pipe Reducer White X2 k Zip Ties X7 not shown Items not included with...

Page 6: ...on Power Drill 7 mm Drill Bit Hammer Drill Bit only necessary to drill into brick or concrete Pencil or Marking Pen Flat Head Screwdriver Pozidiv Screwdriver Small Flathead or Slotted Screwdriver 2 4...

Page 7: ...DO NOT OVERTIGHTEN 8 Double check cell orientation The cell inlet is closest to the cell electrical lead Figure 3 Plumbing Cell Only pH Minus CAUTION Never store acid directly underneath any equipment...

Page 8: ...r pump and before any heating equipment 1 Drill a 9 mm hole in the top of the pipe 2 Ensure the o ring is properly seated on the sensor body 3 Secure the sensor and o ring with the screw clamp provide...

Page 9: ...Input Connection of the pH or pH ORP sensing PCBA PUMP Input Connection of the pH pump for pH Link and Dual Link modules CELL Output 1 Connection of the electrolysis cell UI Output Connection of the...

Page 10: ...ction pipe 5 1 Install the POD Kit 1 Turn off and disconnect all power to the controller 2 For optimal performance the POD must be installed On a 30 cm length of rigid 40 mm or 50 mm PVC pipe As far a...

Page 11: ...rrect port on the POD cap Remove the cap plug if necessary NOTE The ORP sensor is with Dual Link module only Sensor Holder Cap Plug Figure 17 Sensor Holder Installation 2 Carefully remove the protecti...

Page 12: ...pump outlet right 4 Thread tubing through the hole in the cap connect the tubing to the nipple on the module and reattach the threaded cap NOTE For a better fit soften both ends of the tubing by imme...

Page 13: ...ose of the solution according to standard in effect in the country of use 7 Wash the sensor in the diluted hydrochloric acid solution for 2 minutes 8 Rinse sensor in clean tap water for 1 minute Shake...

Page 14: ...ls to the water See Table Turn on the filter pump and Hydroxinator and set it to operate on boost mode This will kick start the sanitizing and hydroxination process Leave the filtration sytem running...

Page 15: ...otal Alkalinity ppm Total Hardness ppm Cyanuric Acid Salinity Level Ideal range After 2 weeks 1 3 7 2 7 6 Concrete 7 0 7 2 Fibreglass 80 120 500 1000 NOTE Total Hardness not Calcium Hardness 30 50 5 0...

Page 16: ...current menu Increase or decrease a setting Lock unlock the UI press and hold both Activate reduced chlorine production mode LED indicates low salt minerals or poor water conductivity The filter pump...

Page 17: ...r at the start of the season Boost mode is used to increase the chlorine level quickly Boost mode lasts for 24 cumulative hours at 100 production output If the program is set to perform hydroxination...

Page 18: ...he top left of the home screen will begin to flash at 15 C 23 04 ON 15 When water temperature is under or equal to 15 C chlorine production automatically switches to the level defined in Low Cover mod...

Page 19: ...CK 3450 8 1 3 Quick Clean Quick Clean is a backwash mode is used to quickly start stop the filter pump single or variable speed pump in order to backwash the filter For variable speed pumps the backwa...

Page 20: ...while Go to Step 2 is selected 11 Rinse the pH sensor with tap water 12 Insert the pH sensor into the pH 4 buffer solution 13 Press while Start is selected 14 Press while Continue is selected 15 Press...

Page 21: ...SETUP BUFFER 470 MV START ORP CALIBRATION PROCEEDING ORP CALIBRATION COMPLETE ORP CALIBRATION 8 5 Setpoint s Current setpoints are displayed on the Home screen whenever the controller is ON PRODUCTIO...

Page 22: ...ugh the pH Setup Menu 8 7 Programming Timers The controller has two internal operating timers The timers are used to define the length of time for the filter pump to operate and the length of time for...

Page 23: ...ess 6 Use to select the minutes for the filtration on time then press 7 Use to select the hour for the filtration off time then press 8 Use to select the minutes for the filtration off time then press...

Page 24: ...versals Water with less calcium can be given more time between reversals Shorter reversal times will cause more wear of your cell plates The polarity reversal interval can be adjusted from 2 to 8 hour...

Page 25: ...the filter pump and chlorine generator close necessary valves and unplug the cell terminal cap 2 Unscrew the retaining ring and remove the electrode If calcium buildup is present immerse the electrod...

Page 26: ...Winterize the pH ORP Sensors It is recommended that the plastic protective caps of the pH and ORP sensors are kept to be used as storage containers The sensors must be stored wet in either a KCl solu...

Page 27: ...ature does not fall back down in order to protect the electric circuits If the box is installed outdoors protect it from direct sunlight Hydroxination will automatically resume once the temperature ha...

Page 28: ...evice is not correctly sized for the pool When the cell is worn calcified or out of order the electrolysis reaction is not efficient Daily filtration and hydroxination times are not sufficient Check t...

Page 29: ...Page 29 MagnaPool Installation Manual NOTES...

Page 30: ...onal S A S U used under license All trademarks referenced herein are the property of their respective owners 2018 Zodiac Pool Systems Inc H0642200_REVA Zodiac Group Australia 219 Woodpark Road Smithfi...

Reviews: