ECI2410 Network Motion Control Card Hardware Manual Version1.4
29
Motor is under control, but
it may oscillate or overturn
sometimes.
Check whether the drive parameters setting
is correct.
Check whether acceleration or deceleration
period and motion speed were set properly in
software.
Motor is under control, but
homing position is
inaccurate.
Check whether the origin signal switch is
working normally
Check whether the origin signal is disturbed.
The position limit signal is
invalid.
Check whether the position limit sensor is
not working normally
Check whether the signal of the limit sensor
is disturbed;
Expansion module can’t be
connected, and the alarm
lights.
Check if the 120Ω resistance is installed
between two sides
Check if several expansion modules use the
same ID.
No signal comes to the
input.
Check whether the IO is supplied normally;
Check whether the input signal level matches
the input channel.
Check whether the input number matches
the ID of the IO board.
The output does not work.
Check whether the IO is supplied normally;
The IO also needs supply.
Check whether the output number matches
the ID of the IO board.
POWER is on, RUN is off.
Check whether the power of power supply is
sufficient, then restart the controller after
adjusting.
RUN is on, ALM is on.
Program running error, please check