Pelletherm V.4 LT
42
performed by a servicing specialist.
Presence of non-ignited
or burned pellets in the
burner zone, but there is
no burning process
If the heating element of the burner, which
ignites the fuel, is damaged then it must be
replaced. If the heating element is
operating normally then the burner
operation parameters have to be adjusted
– to be performed by servicing specialist.
Incorrect operation of the
burner’s photic sensor
Check the photic sensor condition, clean or
replace it if necessary. See the burner’s
manual book.
8. The flame from the
burning process is
dim and the chimney
smokes too much.
Pellets with low quality
Change the pellets as their water content
is probably higher than required for normal
operation.
Improper adjustment of
the pellet burner
operational parameters
Re-adjust the pellet burner operational
parameters – to be performed by a
servicing specialist.
9. Presence of
incompletely burned
fuel in the boiler’s
ash container
Ineffective fuel
combustion
Re-adjust the pellet burner operational
parameters – to be performed by a
servicing specialist.
10. High flue gas
temperature (if a
thermometer is
connected)
Dirty heat exchanging
surfaces of the boiler
Clean the boiler’s heat exchanging
surfaces.
11. Water condensation
over the combustion
chamber surfaces
inside the boiler
Low temperature of the
inlet water
Adjust the circulations pump thermostat.
The recommended circulations water
operational temperature is at least 65
o
C.
12. Presence of smoke
in the boiler room,
after a certain period
of operation
Incomplete sealing of the
boiler cover panels, of
the combustion chamber
door and of the boiler
flange, where the burner
is mounted
The boiler’s door and the cover panels
must be fitted/matched, the sealing ropes
or the burner mounting flange isolation
replaced, and/or tighten the burner to the
boiler – to be performed by a qualified
servicing technician.
13. Heating of the pellet
burner’s fuel feeding
inlet pipe
Insufficient chimney
draught or not cleaned
burner
Clean the appliance and eventually the
chimney. Possible solution is to install
additional flue gas extraction fan and/or to
change the chimney*.
14. Heating of the pellet
burner’s fuel feeding
inlet pipe and
activation of the
emergency
thermostat
Low chimney draught or
dirty appliance
Clean the appliance and eventually the
chimney. It is necessary to restart the
burner. Possible solution is to install
additional flue gas extraction fan and/or to
change the chimney*.
15. Another, not
described failures
Ask for assistance by servicing specialist
or company.
* If the chimney draught values are below the minimum required for reliable
operation of the boiler, it is mandatory to install flue gas extraction fan module.