Pelletherm V.4 LT 

 

 

 

 

 

 

 

 

 

34 

 

6.2.2.  POWER SUPPLYING OF A HOT WATER BOILER “PELLETHERM V.4 LT”. 

 
The  boiler  must  be  connected  to the  electrical  installation,  by  observing  all  technical  safety 
requirements. The boiler delivery kit includes power supply cable with connector.  
 
The fuel hopper and the automated pellet burner from series “GP xx sc” must be filled with 
pellets, in order to be transported by the auger to the burner zone.  

 

6.2.3.  SWITCHING ON THE SYSTEM. 

 
The system switching ON is performed through the switch “POWER”, positioned on the hot 
water  pellet  boiler  from  series  “Pelletherm  V.4  LT”.  In  assignment for  operation,  defined  by 
the  assigned  circulations  water  temperature  in  the  boiler  (and  by  the  assigned temperature 
from a room thermostat – if connected), the automated pellet burner from series “GP xx sc” 
activates  and  transits  to  standby  mode  –  pressing  the  switch  “START”  to  ON  position  will 
start  it.  In  case  the  switch  “START”  has  been  already  in  position  ON  the  pellet  burner  will 
instantly start. If the system has been operated (or is in the so called “hot reserve”), but the 
power  supply  has  been  interrupted, then the  system  will  start  automatically  after the  power 
supply has been restored.   

 

During initial ignition of the pellet burner and insufficient chimney draught (for 
example when the chimney height is not enough or is dirty), smoking from the 
cover panels over the boiler’s combustion chamber and convection zone 
might occur and/or from the combustion chamber’s door. Therefore it is 
recommended to check the closing and sealing of the boiler’s doors and  
cover panels, and also to check the chimney condition. The same effect might  
occur during the transition seasons – autumn and spring, when the natural 
chimney draught is decreased, due to high ambient temperatures.  

 

If the primary (ignition) fuel doze is adjusted incorrectly, smoking through the  
boiler’s unsealed parts might occur. In such cases it is necessary to readjust 
the ignition fuel doze of the pellet burner – 

to be performed by a servicing  

technician. 

 

During the fuel ignition a module activates – electrical heater, positioned  
under the tilted fire-grate of the pellet burner. This heating element heats the 
fuel until it ignites as the presence of fire is indicated by the burner’s photic  
sensor. Detailed information about the construction and operation of the pellet 
burner from series “GP xx sc” is presented in its manual book.   

 

The automated pellet burner from series “GP xx sc” operates through a 
preliminary set algorithm, that is programmed through a specialized software,  
installed in the burner’s control module. The operational parameters of the  
burner must be adjusted only by a trained servicing technician.      

 

6.2.4.  BOILER’S OPERATIONAL PARAMETERS ADJUSTMENT. 

 
The operation mode of the hot water pellet boiler from series “Pelletherm V.4 LT” is directly 
defined by the burner’s control module, defining the assigned circulations water temperature 
in  the  boiler.  The  boiler’s  inlet  circulations  water  temperature  (return  water)  also  influences 
the system operation mode, its reliability and efficiency.   
 

The manufacture company guarantees efficient and reliable operation of the  
system: a hot water pellet boiler from series “Pelletherm V.4 LT” and an  
automated pellet burner from series “GP xx sc”, ONLY within the system’s  
operation range, as presented in Table 4.1 from the manual book.  

 

Summary of Contents for PELLETHERM V.4 LT SERIES

Page 1: ...1 MANUAL FOR INSTALLATION OPERATION AND MAINTENANCE OF A SYSTEM CONSISTING OF A HOT WATER PELLET BOILER FROM SERIES PELLETHERM V 4 LT AND AN AUTOMATED PELLET BURNER FROM SERIES GP xx sc http www green...

Page 2: ...ture company thanks you for your choice The manufacture company submits this manual to help the team that will install adjust and service the system hot water pellet boiler and pellet burner as well a...

Page 3: ...G SECTION COVER CAP 25 5 4 6 INSTALLATION OF THE COVER FLAP IN FRONT OF THE FLUE GAS OUTLET 25 5 4 7 INSTALLATION OF THE BOILER S HORIZONTAL COVER PANELS 27 5 4 8 INSTALLATION OF THE COVER OVER THE BO...

Page 4: ...from series GP xx sc All legal provisions regarding safety All legal provisions regarding environment protection Provisions regarding installation start and adjustment All harmonized provisions of th...

Page 5: ...y the boiler s body heat exchanging surfaces and is then transferred to the heat carrier filled in the system The hot water boiler s delivery kit from series Pelletherm V 4 LT includes Heat exchanger...

Page 6: ...trical which ensures its usage in systems with programmable room thermostat Automatic system operation availability to regulate it through room thermostat weekly programmer guaranteeing maximum heat c...

Page 7: ...hot water boiler s part is the boiler body heat exchanger unit as the automated pellet burner from series GP xx sc is mounted on its side The heat exchanger is offered in 2 variants the so called lef...

Page 8: ...e has been overheated resulting from emergency situations Photo sensor for dynamic control of the burning process System for modulation of the firing air flow rate during the process of initial fuel i...

Page 9: ...Energy efficiency class according to regulation U 2015 1187 Efficiency at nominal heating output mode 92 92 92 CO emissions in the flue gases 0 C 1013 mbar at 10 2 mg m3 163 0 Dust emissions in the fl...

Page 10: ...let burner model GP 20_18 sc GP 25 sc GP 32 sc Boiler weight kg 342 342 362 Boiler water volume l 50 50 60 System overall dimensions B 546 1080 780 1250 546 546 546 W 1080 1080 1080 D 780 780 780 H 12...

Page 11: ...d fuel cogeneration boiler no Combination boiler no Fuel Preferred fuel only one Other suitable fuel s Log wood moisture content 25 no no Chipped wood moisture content 15 35 no no Chipped wood moistur...

Page 12: ...fficiency Auxiliary electricity consumption At rated heat output el n At rated heat output elmax 0 156 kW At 30 50 of rated heat output if applicable elmin 0 134 kW Of incorporated secondary emission...

Page 13: ...moisture content 15 35 no no Chipped wood moisture content 35 no no Compressed wood in the form of pellets or briquettes yes no Sawdust moisture content 50 no no Other woody biomass no no Non woody b...

Page 14: ...fficiency Auxiliary electricity consumption At rated heat output el n At rated heat output elmax 0 156 kW At 30 50 of rated heat output if applicable elmin 0 134 kW Of incorporated secondary emission...

Page 15: ...moisture content 15 35 no no Chipped wood moisture content 35 no no Compressed wood in the form of pellets or briquettes yes no Sawdust moisture content 50 no no Other woody biomass no no Non woody b...

Page 16: ...output if applicable elmin 0 134 kW Of incorporated secondary emission abatement equipment if applicable In standby mode PSB 0 013 kW Contact details Ekoterm Proekt EAD ZMM Haskovo AD 6300 Haskovo 67...

Page 17: ...erm V 4 LT 17 Figure 4 2 System overall sizes front view Figure 4 3 Overall and connection sizes dimensions of a hot water pellet boiler from series Pelletherm V 4 LT pellet burner mounting flange sid...

Page 18: ...Pelletherm V 4 LT 18 Figure 4 4 Overall and connection sizes dimensions of the system rear view Figure 4 5 Overall and connection sizes dimensions of the system top view...

Page 19: ...oiler from series Pelletherm V 4 LT and a pellet burner from series GP xx sc Boiler s convections tract cover Boiler s combustion chamber cover Boiler s combustion chamber cover panel Pellet burner mo...

Page 20: ...cording to standard EN ISO 17225 2 2014 is presented in the automated pellet burner from series GP xx sc manual book Ash container Boiler s combustion chamber door Boiler s combustion chamber First pa...

Page 21: ...et burner from series GP xx sc depends on The adjusted operational heating output of the burner The contamination level on the boiler s heat exchanging surfaces The sealing level of the boiler combust...

Page 22: ...nt of the boiler must be at least 1000 mm The minimum allowed distance between the boiler s rear side and a wall must be at least 400 mm The minimum distance between the boiler side where the pellet b...

Page 23: ...nnect the hot water pellet boiler from series Pelletherm V 4 LT to the heating installation by using proper fittings and accessories to be performed in accordance to the preliminary prepared technical...

Page 24: ...ing of the pellet burner After the burner has been mounted the connection screws must be tightened equally in order to ensure proper sealing between the flange and the boiler body Figure 5 3 View of m...

Page 25: ...F THE ASH CLEANING SECTION COVER CAP Figure 5 5 The cover cap for cleaning of the ash residues positioned after the second flue pass of a hot water boiler from series Pelletherm V 4 LT is properly pos...

Page 26: ...rmal loads therefore it symmetrically manufactured It is recommended to turn the cover flap on every two to three weeks of operation Figure 5 6 The directing cover flap is dismounted and the boiler s...

Page 27: ...letherm V 4 LT 5 4 8 INSTALLATION OF THE COVER OVER THE BOILER S CONVECTION TRACT This cover is equipped with protection element made of stainless steel Figure 5 9 Directing cover over the boiler s co...

Page 28: ...l There are connectors to power supply to burner and to room thermostat Depending on whether it is with left or right burner mounting the connectors are positioned on the same boiler cover side as the...

Page 29: ...to change the system construction without engagement to inform the end users 5 4 13 CONNECTING THE SYSTEM TO THE POWER SUPPLY Connecting the system consisting of a hot water pellet boiler from series...

Page 30: ...ay mixing valve 10 Circulations pump 2 The exemplar hydraulic scheme is only informative and can not be practically used as implemented hydraulic scheme The installation and warm tests completion of t...

Page 31: ...When initiating the system to operation consisting of a hot water pellet boiler from series Pelletherm V 4 LT and a pellet burner from series GP xx sc the following main requirements must be observed...

Page 32: ...rheating It is factory adjusted to stop the automated pellet burner from series GP xx sc power supply in case the circulation water temperature exceeds the limit adjusted in the factory to 95 o C Swit...

Page 33: ...Description of the electrical connectors installed on the boiler s interface panel Room thermostat connector Switch START Communication connector Pellet burner connector Emergency thermostat Switch PO...

Page 34: ...and also to check the chimney condition The same effect might occur during the transition seasons autumn and spring when the natural chimney draught is decreased due to high ambient temperatures If th...

Page 35: ...ON the button POWER but only after the failure reason has been eliminated The ash content does not change significantly the fuel s calorific value but requires special construction of the burner in or...

Page 36: ...n be performed by decreasing the burner s heating output level For detailed information see the burner s manual book Do not decrease the burner s heating output below the system s minimum output becau...

Page 37: ...ted in its manual book In case the system operation is stopped a complete cleaning from the ash residues over the boiler s heat exchanging surfaces must be performed because the ash has corrosive infl...

Page 38: ...ompany that services and maintains the system 6 8 USER INTRODUCTION TO THE PROCEDURES FOR MAINTENANCE AND ADJUSTMENTS OF THE SYSTEM It is necessary that the user is completely introduced with the pres...

Page 39: ...e boiler s bottom gather the ash residues in fire proof or another proper container after that in reverse order mount the ash container back and close the door mount the other cover panels of the boil...

Page 40: ...the hot water pellet boiler Risks from electrical shock by indirect contact The boiler and the burner are connected to the power supply network and the control modules are positioned in the interface...

Page 41: ...ut It is necessary to adjust the burner s heating output level High temperature assignment by the room thermostat if connected It is necessary to decrease the room thermostat temperature assignment 3...

Page 42: ...er the combustion chamber surfaces inside the boiler Low temperature of the inlet water Adjust the circulations pump thermostat The recommended circulations water operational temperature is at least 6...

Page 43: ...using a room thermostat Use the room thermostat socket only Do not supply external voltage Remove the bridge connection when using a room thermostat Use the room thermostat socket only Do not supply e...

Page 44: ...Pelletherm V 4 LT 44 Figure 8 1 Control panel wiring diagram of a hot water pellet boiler from series Pelletherm V 4 LT co operating as a system together with a pellet burner from series GP xx sc...

Page 45: ...Pelletherm V 4 LT 45 Figure 8 2 Wiring diagram of the boiler s connector panel used to connect the pellet burner...

Page 46: ...Pelletherm V 4 LT 46...

Page 47: ...dical maintenance presented in the present manual book are not observed Attempts to recover any defects performed by the buyer or by other unauthorized persons Changes in the system s appliances const...

Page 48: ...Pelletherm V 4 LT 48...

Reviews: