Pelletherm V.2 M01 41
Figure 6.12. Choosing a degree of thermal power of boiler "Pelletherm V.2 M01".
With buttons "+" and "-" is selecting the desired degree of thermal power for
the boiler. Then is pressed the "S" button to confirm the selection of operation
at the given degree, to exit the menu press the button "ESC".
6.2.13. ACTIVATION OF OPTION “OPERATION WITH HEAT ACCUMULATOR
(BUFFER)”.
A NECESSARY CONDITIONS:
Preliminary from the manufacturing company must be activated option DUAL NTC POP = 1.
This option is in the Super user menu, access to which is only for the Factory Company or
Authorized Service Center.
ACTIVATION:
In the
Advanced menu
, parameter
Thermostat
, when enabled in
Super user menu
parameter
DUAL NTC POP
, occur following operating opportunities for integrated
thermostat:
THERMOSTAT:
Thermostat type:
"Ëxternal 230 VAC" - never used!
"Temp A" - is not usually used;
"Room + Temp A" - usually used in all facilities without heat accumulator
-
default
;
"Temp BC" - is not usually used;
"Temp BC + Room" - usually used in facilities with heat accumulator.
During the operation with heat accumulator is selected
"Temp BC + Room".
In this case
operates three NTC sensors:
Sensor A - water temperature in the boiler;
Sensor B - water temperature at the upper part of the heat accumulator;
Sensor C - water temperature at the lower part of the heat accumulator.