Chapter 5: System configuration
96
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
The system bus range of addresses is preprogrammed by default to carry out
certain functions, for example, to illuminate zone LEDs. Alternatively, addresses
9.001 to 9.128 can be configured to be freely programmable. Where connected
outputs are set to addresses in the system bus range, then these outputs
automatically mimic the behaviour of the preprogrammed functions. For example,
an output board set to the same address as the zone LEDs automatically mimics
these LEDs, without any panel programming being required.
The user bus range of addresses is freely programmable. Any output connected
to the system with an address in the user bus range must be programmed using
the I/O-mapping function before it will operate.
The ZP3 auxiliary boards can be set to assume any address in the system bus
(group 9) or user bus (group 10) address range. Auxiliary boards have 8, 16, or
24 points, which are addressed sequentially from a base address. The base
address is determined by the DIP switch settings on each board. Refer to the
information in the topic “System address list” on page 97.
DIP switch settings between 0 and 31 set the addresses within the system bus
(group 09) range (Switch 8 = ON).
DIP switch settings between 32 and 127 set the addresses within the user bus
(group 10) range (Switch 8 = OFF).