Appendix B: ZP3 system maintenance
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
135
8
"
7
1
(
5.
Completion of
service
Restore the system to normal condition, enable any disabled
devices, reconnect any disconnected devices, reconnect all
external systems that were disconnected for the testing, and
ensure that the system is left in 100% working condition. Advise
all staff and the remote manned centre that testing is complete,
and that any alarm now received must be treated as real.
The panel has built-in software functions for providing maintenance diagnostics
and support. These functions are accessed via the Maintenance menu, using the
panel keypad. Menu functions are displayed on the LCD screen.
Access to the menus is via the panel keypad (see Figure 64). Each button on the
keypad is described in Table 42 on page 136.