10.24
ZA-Intern menu
Parameterisation of internal measuring and monitoring functions
Parameter
Description
Value range
Factory set-
ting
PW_S9
Password for the indication of additional parameter
0
UVW_CHK
De
fi
nition of motor phase checking on start-up
Single:
1.Motor phases will be check with the
fi
rst travel after
switching-on the inverter. With a successful control no more
further examination is made.
If the examination is incorrect, with each start an examination is
made until a correct examination could be accomplished.
Cont:
Motor phases will be check with each travel
Off:
Checking of the motor phases is deactivated
Single
Cont
Off
Single
UVW_PEK
Test voltage for motor phase check
1 ... 10 V:
Selection of the test voltage between 1 V and 10 V.
In case of an error the testing voltage is displayed in the error
message.
15 V:
Test voltage 15 V.
f(P):
The testing voltage depends on the nominal voltage of the
motor, which is entered in the menu "Motor name plate". In case
of an error the testing voltage is displayed in the error message.
1 ... 10 V
15 V
f(P)
f(P)
n_ANA
Initialisation value for analogue input in ZETADYN 3-HY
Example:
n_ANA = 3000
analogue input = 0-10 V
10 V = 3000 1/min
1 ... 3300
3000
Original operating instructions
ZETADYN 3C
Parameter list
R-TBA08_03-GB 1619
Part.-No. 00163322-GB
98/204