10.19
Safety gear menu
Con
fi
guration of the data used for the "Safety gear" function.
The procedure for the safety brake is described in the "Special functions" chapter.
Parameter
Designation
Value range
Factory set-
ting
SB_MOD
Activate or deactivate the capture release
OFF:
Capture release is deactivated
On:
Starting the Safety-Brake-function in the requested direction
by pressing the button "Inspection trip UP" oder "Inspection trip
DOWN"
On
Off
Off
SB_M
Default for pulse amplitude with which the motor is to be fed with
current.
The default is calculated as a percentage of the maximum
operating current of the frequency inverter (nominal current x 1.8)
10 ... 100 %
70
SB_T0
Pulse breake
Break time between the individual current pulses
0.1 ... 2.0 s
0.2
SB_T1
Î
mpulse time
Time for which the motor will be fed with current
0.1 ... 1.0 s
0.5
SB_N
Number of current pulses
1 ... 5
3
1
SB_M [%]
100
SB_N=3
SB_T1
SB_T0
t
Process capture release
1
Inspection trip "UP" or "DOWN"
10.20
HW-Ident. menu
Identifying the individual assemblies of the ZAdyn4B. The identi
fi
cation of the assembly is generally
read out directly from its EEPROM.
Parameter
Designation
Value range
Factory set-
ting
ID_NOK
The number of the changed hardware identi
fi
ca-
tion (identi
fi
cation-no. unequal 0) is indicated
10.21
Power section menu
Con
fi
guring the tolerances of the internal power stage.
Parameter
Designation
Value range
Factory set-
ting
M_PWM
Pulse width modulation operating mode
Auto:
PWM frequency is changed depending on the power
stage temperature and load.
At the start of travel, the motor voltage is cycled at the cycle
frequency set in parameter "f_PWM_H".
Cycle frequency is reduced if required.
Fix f_PWM:
motor voltage is permanently cycled at the PWM
frequency set in the parameter "f_PWM"
Auto
Fix f_PWM
Auto
f_PWM
Cycle frequency at parameter setting "M_PWM=Fix f_PWM"
2.5 ... 10.0 kHz
8.0
Original operating instructions
ZAdyn4B 110-180
Parameter list
R-TBA15_01-GB 2014 Index 005
Part.-No. 00163453-GB
93/200