5.3
Wiring
The cores of the power line, motor line and the brake resistor line are routed through the channels on
the top and bottom of the housing (see
fi
g.).
Power line
Channels on the bottom
Motor cable
Channels on the top, left
Brake resistor cable
Channels on the top, right
1
Cable routing on bottom ZAdyn4B
1
Channels for power line
2
Cable routing on top ZAdyn4B
2
Channels for brake resistor line, motor line
5.4
Protective ground connection
In accordance with the de
fi
ned networks in DIN EN 60990 the frequency inverter has a leakage
current > 3.5 mA and must therefore be permanently connected. In accordance with EN 50178 item
5.2.11 and 5.3.2.1, the PE conductor connection must have a cross-section of at least 10 mm
²
. In the
case of PE conductors < 10 mm
²
, an additional PE conductor must be connected. The cross-section
must correspond at least to the cross-section of the PE conductor on the connecting lead. ZAdyn4B
M6 threaded bolts are available on the ZETADYN for connecting the PE conductors (see
fi
g.).
PE conductor connection
ZAdyn4B
Original operating instructions
ZAdyn4B 110-180
Electrical installation
R-TBA15_01-GB 2014 Index 005
Part.-No. 00163453-GB
22/200