MOD5 (standard setting for synchronous motors)
The drive is position-controlled. Up to the end of T_2, the drive position is recorded and corrected if
there is a change. The parameter "K_START" is the position controller ampli
fi
cation. It is activated at
the start of T_1 and deactivated at the end of T_2.
MOD4
Corresponds to the MOD5. function. The parameter "s_start" is activated additionally. If the drive
position changes during the time T_2 by the value entered in "s_start", "K_START" is switched off.
This prevents the drive from being damaged by too high a value of "K_START".
Start-up variations
RF
Controller enable
V_1
Positioning speed
V_3
Travel Speed
RV1 / RV2
Direction default
RB
Controller ready
MB_Brake
Mechanical brake
T_1
Flux build-up time
T_2
Brake opening time
T_3
Speed=0
K_START
MOD1 / MOD2 (Speed control)
MOD3 (position- & speed control)
MOD4 / MOD5 (position control)
SPD_KP
Base ampli
fi
cation speed controller
11.4
Optimizing the acceleration
The acceleration torque is de
fi
ned by the parameter in the
Accelerating
menu. By changing the
parameter values, you can adapt the curve shape to the requirements
Acceleration ramp
RF
Controller enable
V_1
Positioning speed
V_3
Travel Speed
RV1 / RV2
Direction default
RB
Controller ready
MB_Brake
Mechanical brake
Original operating instructions
ZAdyn4B 110-180
Travel options
R-TBA15_01-GB 2014 Index 005
Part.-No. 00163453-GB
109/200